REPLACING THE I/O MODULES
6
- 37
Specifications
AJ55TB32-8DT
A20XB-16UD
Compat-
ibility
Precautions for
replacement
Operation indicator
ON indication (LED)
ON indication (LED)
External wiring method
24-point terminal block (M3 screw)
Transmission circuit included
40-point terminal block (M3 screw)
Transmission circuit included
Wiring must be changed.
Existing wires can be used but
applicable crimping terminals
are different.
For details, refer to Section
6.3.
Applicable wire size
0.75 to 2mm
2
0.3 to 1.25mm
2
(when the following applicable crimping
terminals are used: 0.75 to 2mm
2
)
Applicable crimping
terminal
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
For wire sizes 0.75 to 2mm
2
R2-3SL, RAV2-3SL, RAP2-3SL,
VD2-3S, VD2-3.5SS, VD2-3.5S,
VDAV2-3.5SS, VDAV2-3.5S
I/O module
power
supply
Voltage
15.6 to 27.6VDC
21.6 to 27.6VDC
(ripple voltage 0.5Vp-p or less)
Operating voltage range is
different.
Current
50mA
106mA
Because the current
consumption has increased,
the current capacity must be
reviewed.
External dimensions
50(H) × 114(W) × 66(D) mm
40(H) × 190(W) × 60(D) mm
The shape is different.
Installation method
Screw mounted
Screw mounted
×
Because mounting hole size is
different, reworking is
required.
Mounted to DIN rail
Mounted to DIN rail
The A20XB-16UD can be
mounted to the existing DIN
rail.
Weight
0.3kg
0.3kg