6
REPLACING THE I/O MODULES
6
- 4
I/O module
AJ55TB32-8DR
(when negative common
type is used)
A20SB-04US
+ A20PB-04RS
(1) External wiring: Changed
(2) Number of modules: Changed (Two modules are required.)
(3) Program: Changed
(4) Specifications:
(Input part)
Rated input voltage: Not changed
Rated input current: Not changed
ON voltage/ON current: Changed
OFF voltage/OFF current: Changed
Input resistance: Not changed
(Output part)
Rated load voltage: Changed (The voltage that can be used is equivalent.)
Rated load current: Not changed
Maximum switching frequency:
Changed (3600 times/hour
20 times/minute)
(5) Functions: Changed
(Input part)
Wiring: 3-wire
2-wire
A positive common type cannot be used.
(Output part)
4 points/common
All points independent
AJ55TB32-16DR
(when positive common
type is used)
A20SB-08UD
+ A20PB-08RS
(1) External wiring: Changed
(2) Number of modules: Changed (Two modules are required.)
(3) Program: Changed
(4) Specifications:
(Input part)
Rated input voltage: Not changed
Rated input current: Not changed
ON voltage/ON current: Changed
OFF voltage/OFF current: Changed
Input resistance: Not changed
(Output part)
Rated load voltage: Changed (The voltage that can be used is equivalent.)
Rated load current: Not changed
Maximum switching frequency:
Changed (3600 times/hour
20 times/minute)
(5) Functions: Changed
(Input part)
A negative common type cannot be used.
(Output part)
8 points/common
All points independent
AJ55TB32-16DR
(when negative common
type is used)
A20SB-08USD-1
+ A20PB-08RS
(1) External wiring: Changed
(2) Number of modules: Changed (Two modules are required.)
(3) Program: Changed
(4) Specifications:
(Input part)
Rated input voltage: Not changed
Rated input current: Not changed
ON voltage/ON current: Changed
OFF voltage/OFF current: Changed
Input resistance: Not changed
(Output part)
Rated load voltage: Changed (The voltage that can be used is equivalent.)
Rated load current: Not changed
Maximum switching frequency:
Changed (3600 times/hour
20 times/minute)
(5) Functions: Changed
(Input part)
A positive common type cannot be used.
(Output part)
8 points/common
All points independent
I/OLINK series model
AnyWire DB A20 series alternative model
Product
Model name
Model name
Remarks (restrictions)