MELSEC-A
3 SPECIFICATION
3.6.4 CH.
output range setting (Address RWwm+9
H
, RWwm+A
H
)
(1) Set the analog output range per channel.
(2) Operation is performed according to the setting made for the leading edges of
initial data setting request flag (RY(n+9)).
(3) The default settings are -10 to 10V for all channels.
b15
b12
b11
b8
b7
b4
b3
b0
to
CH.4
to
CH.3
to
CH.2
to
CH.1
RWwm+9
b15
b12
b11
b8
b7
b4
b3
b0
to
CH.8
to
CH.7
to
CH.6
to
CH.5
RWwm+A
Output range
Seting value
-10 to 10V
0
H
0 to 5V
1
H
1 to 5V
2
H
User range setting 1 (-10 to 10V)
3
H
User range setting 2 (0 to 5V)
4
H
POINT
If the set value is outside the setting range, error "20
" occurs, the "RUN" LED
flickers at intervals of 0.1s, and all channels do not make D/A conversion.
indicates the channel No. where the error occurred.
3.6.5 HOLD/CLEAR setting (Address RWwm+B
H
)
(1) Set HOLD/CLEAR to each channel.
(2) Operation is performed according to the setting made for the leading edges of
initial data setting request flag (RY(n+9)).
(3) The default settings are CLERA for all channels.
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
CH.2 CH.1
b0
Ignored
0: CLEAR
1: HOLD
CH.4 CH.3
CH.6 CH.5
CH.8 CH.7
Содержание AJ65VBTCU-68DAVN
Страница 1: ...Digital Analog Converter Module type AJ65VBTCU 68DAVN User s Manual ...
Страница 2: ......
Страница 6: ...A 4 A 4 CONDITIONS OF USE FOR THE PRODUCT ...
Страница 13: ...A 11 A 11 MEMO ...
Страница 18: ...2 2 2 2 MELSEC A 2 SYSTEM CONFIGURATION 2 Remote net ver 2 mode remote net additional mode 2 ...
Страница 41: ...3 19 3 19 MELSEC A 3 SPECIFICATION MEMO ...
Страница 77: ...5 11 5 11 MELSEC A 5 PROGRAMMING 2 Program example ...
Страница 79: ...5 13 5 13 MELSEC A 5 PROGRAMMING ...
Страница 82: ...5 16 5 16 MELSEC A 5 PROGRAMMING ...
Страница 84: ...5 18 5 18 MELSEC A 5 PROGRAMMING Remote registers RWw RWr ...
Страница 92: ...5 26 5 26 MELSEC A 5 PROGRAMMING Remote registers RWw RWr ...
Страница 99: ...5 33 5 33 MELSEC A 5 PROGRAMMING MEMO ...
Страница 111: ......