3 - 12 3 - 12
MELSEC-A
3 SPECIFICATION
3.5.2 Functions of the remote I/O signals
Table 3.6 explains the functions of the remote I/O signals of the AJ65VBTCU-68DAVN.
Table 3.7 Remote I/O Signal Details (1/2)
Device No.
Signal Name
Description
RXnC
E
2
PROM write error flag
Turns on the number of E
2
PROM write times exceeds its limit (1000,000 times per
channel). If this flag has turned on, this module itself has failed (hardware fault) and
therefore this flag cannot be reset (turned off) by the error reset request flag.
At occurrence of this error, power on the AJ65VBTCU-68DAVN again. If this flag turns
on after the power is switched on again, it is a hardware fault. Contact your nearest
Mitsubishi representative.
RX (n+1) 8
Initial data processing request
flag
After power-on, the initial data processing request flag is turned on by the AJ65VBTCU-
68DAVN to request the initial data to be set.
Also, after the initial data processing is complete (initial data processing complete flag
RY (n+1) 8 ON), the flag is turned off.
RX (n+1) 9
Initial data setting complete flag
When the initial data setting request (RY (n+1) 9 ON) is made, the flag turns on after
the initial data setting completion is done.
Also, after the initial data setting is complete, the initial setting complete flag turns off
when the initial data setting request flag turns off.
RX (n+1) A Error status flag
Turns on at occurrence of the output range setting error, digital value setting error or
E
2
PROM write error (RXnC).
Does not turn on at occurrence of the watchdog timer error.
(The "RUN" LED goes off.)
RX (n+1) B Remote READY
Turns on when initial data setting is completed after power-on or at termination of the
test mode.
(Used for interlocking read/write from/to the master module.)
n: Address allocated to the master module by station number setting.
Содержание AJ65VBTCU-68DAVN
Страница 1: ...Digital Analog Converter Module type AJ65VBTCU 68DAVN User s Manual ...
Страница 2: ......
Страница 6: ...A 4 A 4 CONDITIONS OF USE FOR THE PRODUCT ...
Страница 13: ...A 11 A 11 MEMO ...
Страница 18: ...2 2 2 2 MELSEC A 2 SYSTEM CONFIGURATION 2 Remote net ver 2 mode remote net additional mode 2 ...
Страница 41: ...3 19 3 19 MELSEC A 3 SPECIFICATION MEMO ...
Страница 77: ...5 11 5 11 MELSEC A 5 PROGRAMMING 2 Program example ...
Страница 79: ...5 13 5 13 MELSEC A 5 PROGRAMMING ...
Страница 82: ...5 16 5 16 MELSEC A 5 PROGRAMMING ...
Страница 84: ...5 18 5 18 MELSEC A 5 PROGRAMMING Remote registers RWw RWr ...
Страница 92: ...5 26 5 26 MELSEC A 5 PROGRAMMING Remote registers RWw RWr ...
Страница 99: ...5 33 5 33 MELSEC A 5 PROGRAMMING MEMO ...
Страница 111: ......