3. SPECIFICATIONS
MELSEC-A
3-12
Device No.
Signal name
Description
After power on or a hardware reset, this is turned on because the AJ65BT-68TD
requests the initial data setting .
After the initial data processing is complete (initial data processing request flag
RY(n+7)8 is turned on), it turns off.
Turns on when initial data setting request (initial data setting request flag RY(n+7)9 is
turned on) is made.
After the initial data setting request flag is turned off when initial data setting is
complete, this also turns off.
RX (n+7) A
Turns on when wire breakage detection flag/write data error flag/E
2
PROM error flag
turns on.
After the cause of the error has been removed, the flag may be reset (off) by turning
on the error reset request flag, but since the E
2
PROM error flag cannot be reset, this
flag may also not be reset.
RX (n+7) B
After power on or a hardware reset, this flag turns on when the initial data setting is
complete and the detected temperature value at the conversion-enabled channel has
been stored in the remote register.
Will not turn on when all channels are conversion disabled.
It will turn off for two seconds when the offset/gain switch is set to [OFFSET] during
test mode or when changed from [GAIN] to [SET].
Used as an interlock for read and write in respect to the master module.
Initial data
processing
request flag
RX (n+7) 8
Initial data
setting
completion
flag
RX (n+7) 9
Error status
flag
Remote
READY
Downloaded from
Содержание AJ65BT-68TD
Страница 2: ...Downloaded from ManualsNet com search engine ...
Страница 57: ...5 PROGRAMMING MELSEC A 5 8 3 Program example Downloaded from ManualsNet com search engine ...
Страница 102: ...APPENDIX MELSEC A A 27 Appendix 4 External Dimensions Diagram Downloaded from ManualsNet com search engine ...
Страница 103: ...APPENDIX MELSEC A A 28 MEMO Downloaded from ManualsNet com search engine ...
Страница 105: ...Downloaded from ManualsNet com search engine ...