3. SPECIFICATIONS
MELSEC-A
3-18
3.8.5
Sampling processing/travel average processing designation
The AJ65BT-68TD may designate sampling processing or travel average processing for each
individual channel.
The setting of sampling processing or travel average processing is made through the CH.
sampling
processing/travel average processing designation flags (RYn8 to RYnF).
Setting Description
ON
Travel average processing
OFF Sampling
processing
(1) Travel average processing
The average of the four detected temperature values that have been taken during each sampling
time (current value + three previous values) is calculated and stored in the remote register.
Also, since the average processing travels for each sampling, the most recent measured
temperature value may be obtained.
By using this, a scaling value can be obtained using the detected temperature value that has
undergone the average processing and stored in the remote register.
4
+
+
+
4
+
+
+
4
+
+
+
1st storage
1st storage
2nd storage
3rd storage
2nd storage
3rd storage
The data transition inside the remote register
Sampling time
T
em
pe
ra
tu
re
[°C]
Time [ms]
Remote register
Detected
temperature
value
Downloaded from
Содержание AJ65BT-68TD
Страница 2: ...Downloaded from ManualsNet com search engine ...
Страница 57: ...5 PROGRAMMING MELSEC A 5 8 3 Program example Downloaded from ManualsNet com search engine ...
Страница 102: ...APPENDIX MELSEC A A 27 Appendix 4 External Dimensions Diagram Downloaded from ManualsNet com search engine ...
Страница 103: ...APPENDIX MELSEC A A 28 MEMO Downloaded from ManualsNet com search engine ...
Страница 105: ...Downloaded from ManualsNet com search engine ...