6 - 13 6 - 13
MELSEC-GOT
6 HANDLING
d) CC-Link connection (CC-Link dedicated cable)
•
Peel the sheath ( with the length shown below) at both ends of the
cable, and expose the shield braided wire for grounding.
•
When using a CC-Link dedicated cable between GOT and PLC
130
130
GOT side
PLC side
Within 230
Within 400
40
40
Unit : mm (inch)
Ferrite Core
(ZCAT3035-1330)
(5.12)
(5.12)
(9.06)
(15.75)
(1.57)
(1.57)
•
When using a CC-Link dedicated cable between GOT and GOT
130
130
GOT side
GOT side
Within 230
40
40
Unit : mm (inch)
Ferrite Core
(ZCAT3035-1330)
Within 230
(5.12)
(5.12)
(9.06)
(9.06)
(1.57)
(1.57)
e) Ethernet Connection (Twisted pair shielded cable)
•
Peel the sheath (with the length shown below) at both ends of the
cable, and expose the shield wire for grounding.
GOT side
Ethernet module side
Within 230
(9.06)
Within 400
(15.75)
40
(1.57)
40
(1.57)
Unit : mm (inch)
130
(5.12)
Ferrite core
(ZCAT3035-1330)
f) Printer cable
•
Wind cable shield material around the cable, and pull out the
grounding braided wire of the cable shield material with the length
shown below.
Within 150
(5.90)
GOT side
130
(5.12)
Unit : mm (inch)
Printer side
Ferrite Core (ZCAT3035-1330)
Grounding braided wire (50mm(1.97inch))
Cable shield material