7
*3
Use impossible at local station.
No.
Name
Description
(2)
Station number
setting switch
AJ61BT11
A1SJ61BT11
Set the module station number.(setting at shipment: 0)
<Range>
• In the remote net mode
Master station: 0
Local station: 1 to 64
Standby master station: 1 to 63
The "SW" and "L ERR." LEDs are turned on when a value
other than 0 to 64 is set.
In the remote I/O net mode
Master station: 1 to 64 (set the last station number of remote
I/O station)
When set to 0, the "PLM" LED is turned on.
(3)
Mode setting switches
AJ61BT11
A1SJ61BT11
Set the module operation status. (setting at shipment: 0)
Number
Name
0
Online (remote net mode)
1
Online (remote I/O net mode)
2
Offline
3
Line test 1 *3
4
Line test 2 *3
5
Parameter confirmation test *3
6
Hardware test
7
Setting error (the "SW" LED on)
8 to A
Setting prohibited
B to F
Setting error (the "SW" LED on)
(4)
Transmission speed
setting switch
AJ61BT11
A1SJ61BT11
Set the module transmission speed.
(setting at shipment: 0)
Number
Setting detail
0
156kbps
1
625kbps
2
2.5Mbps
3
5Mbps
4
10Mbps
5 to 9
Setting error (the "SW" and "L ERR" LED on)
X1
X10
STATION NO.
STATION NO.
1
X
10
X
1:ONLINE(RIM)
2:OFFLINE
0:ONLINE(A.R.)
MODE
MODE
10M
5M
2.5M
625K
156K
4
3
2
1
0
B RATE
B RATE
10M
5M
2.5M
625K
156K
4
3
2
1
0