A-4
Address (Hex.)
CH1 CH2 CH3 CH4
Buffer memory address name
Setting/selection range
32 52 72 92 AUTO/MAN mode switch
0 : Auto(AUTO),
1 : Manual(MAN)
33 53 73 93 Manual output setting
-50 to 1050
(-5.0% to 105.0%)
34 54 74 94 Setting change rate limiter
0 to 1000(0.0 to
100.0%min)
35 55 75 95 AT bias
±
Input range width
36 56 76 96 Forward/reverse action setting
0 : Forward action,
1 : Reverse action
37 57 77 97 Upper setting limiter
38 58 78 98 Lower setting limiter
Within measurement range
39 59 79 99 CT selection
0 : 0.0 to 100.0A,
1 : 0.00 to 20.00A
3A 5A 7A 9A Heater disconnection alert setting
0 to 100%
3B 5B 7B 9B Loop disconnection detection determination time
0 to 7200s
3C 5C 7C 9C Loop disconnection detection dead band
Input range width
3D 5D 7D 9D Unused channel setting
0 : Used, 1 : Unused
3E 5E 7E 9E
3F 5F 7F 9F
Unusable
—
A0
Alert alarm 1 mode setting
A1
Alert alarm 2 mode setting
A2
Alert alarm 3 mode setting
A3
Alert alarm 4 mode setting
0 to 14
A4
Alert blind section setting
0 to 100(0.0 to 10.0%)
A5
Number of alert delays
0 to 255
A6
Number of delays for heater disconnection/
current error detection when output is turned off
3 to 255
A7
Temperature increase complete determination
1 to 10
°
C(
°
F)
A8
Temperature increase complete soak time set-
ting
0 to 3600min
A9
PID continue flag
0 : Stop, 1 : Continue
AA
Heater voltage compensation function setting
0 : OFF, 1 : ON
AB AC AD AE Standard heater current value
Heater current range
AF
Transistor output monitor or delay time setting
0 to 50(0 to 500ms)
B0
CT monitor method switch
0 : on current/off current,
1 : on current