MITSUBISHI ELECTRIC 9900CX SERIES UPS
9900CX SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-5
Table 3.6
Crimp Type Compression Lug
WIRE
SIZE
WIRE
STRAND
RECOMMENDATION
CRIMP TOOL REQUIRED
BURNDY TYPE Y35 OR Y46
(CODE)
CLASS
VENDOR
CAT. NO.
COLOR KEY
DIE INDEX
400 MCM
B
I
BURNDY
ILSCO
BURNDY
YA32
CRA-400L
YA36-LB
BLUE
BLUE
---
19 / 470
19 / 470
1027
500 MCM
B
I
BURNDY
ILSCO
BURNDY
YA34
CRA-500L
YA38-LB
BROWN
BROWN
---
20 / 299
20 / 299
1029
600 MCM
B
I
BURNDY
ILSCO
BURNDY
YA36
CRA-600L
YA39-LB
GREEN
GREEN
---
22 / 472
22 / 472
1030
750 MCM
B
BURNDY
ILSCO
YA39
CRA-750L
BLACK
BLACK
24
24
NOTE: When using crimp type lugs, the lugs should be crimped to the specifications given
in the manufacturer's instructions for both crimp tool and lug.
Figure 3.1
UPS Terminal Designation
Bypass Module
CB3
CONVERTER / INVERTER
CHARGER
52C
Static Transfer
Switch
52S
CB1
CB2
UPS Module
CONVERTER / INVERTER
CHARGER
52C
CB1
CB2
UPS Module
CONVERTER / INVERTER
CHARGER
52C
CB1
CB2
UPS Module
UPS
CABINET
AC
input
Battery
Cabinet
Bypass
Input
Output
Terminals
A40
B40
C40
Terminals
A
B
C
Terminals
BP
BN
Terminals
A50
B50
C50
~ ~
~
~
3
~
6 UPS
modules
Содержание 9900C Series