MITSUBISHI ELECTRIC 9900CX SERIES UPS
9900CX SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-15
1.5 SPECIFICATIONS
The UPS nameplate displays the rated kVA as well as nominal voltages and currents. The
nameplate is located on the backside of the Bypass Module door.
Table 1.3
Power Specifications
Rated output
Power
Input voltage
3 phase / 3 wire
Bypass input voltage
3 phase / 3 wire
Output voltage
3 phase / 3 wire
1050kVA / 1000kW
480V
480V
480V
1400kVA / 1330kW
480V
480V
480V
1750kVA / 1660kW
480V
480V
480V
2100kVA / 2000kW
480V
480V
480V
Table 1.4
UPS Cabinet Information
UPS
[kVA]
Cable
Entry
Width
[in / mm]
Depth
[in / mm]
Height
[in / mm]
Weight
[lb./ kg]
Heat Loss
[kBTU / h]
1050 BOTTOM / TOP 118.2 / 3003.2
35.5 / 901.6
80.7 / 2048.6
6283 / 2850
127.6
1400 BOTTOM / TOP 167.3 / 4250
35.5 / 901.6
80.7 / 2048.6
9580 / 4350
159.7
1750 BOTTOM / TOP 198.8 / 5050
35.5 / 901.6
80.7 / 2048.6
11770/ 5350
199.7
2100 BOTTOM / TOP 222.4 / 5650
35.5 / 901.6
80.7 / 2048.6 13530 / 6150
239.6