MITSUBISHI ELECTRIC 9900CX SERIES UPS
9900CX SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
2-14
The UPS is equipped with a selectable input contact item. The above items are the default
settings. Table 2.2 shows the selectable items for input contacts.
Table 2.2
Selectable Items for Input Contacts
No.
Input Item
Default
0 NONE
1 REMOTE
START
IN1
2 REMOTE
STOP
IN2
3 POWER
DEMAND
1
IN4
4 POWER
DEMAND
2
5
BATTERY LIQUID LOW
6 BATTERY
TEMP.ABNORMAL
IN3
7 GENERATOR
OPERATION
8 ASYNCHRONOUS
9 ANOTHER
BUS
SYNC.
10
REMOTE INVERTER(MMS)
11
REMOTE BYPASS(MMS)
12
EXT.BYP dV STR
13
USE IB LIMIT 2
14
CHARGER STOP
15
EXTERNAL ALARM
16
CB2 EX
17
CHARGE DEVICE ERR
18
CONVERTER OPE. PROHIBITION
19
REMOTE MOD.START
20
REMOTE MOD.STOP
21
SPARE 21
22
SPARE 22
23
SPARE 23
24
SPARE 24
25
SPARE 25
26
SPARE 26
27
SPARE 27
28
SPARE 28
29
SPARE 29
30
SPARE 30
31
TRACE TRIGGER
NOTE: Contact MITSUBISHI ELECTRIC POWER PRODUCTS, INC for Detailed
information.
CAUTION :
In all cases, a switch having a protective cover is recommended in order
to reduce the possibility of accidental operation.