SPECIFICATIONS
The UPS name plate displays the rated kVA as well as nominal voltages and currents. The
name plate is located on the inside of the UPS front door.
TABLE 1.3
Power Specifications
Rated output
Power
Input voltage
3 phase / 3 wire
Bypass input voltage
3 phase / 4 wire
Output voltage
3 phase / 3 or 4 wire
100kVA /
80kW
150kVA / 120kW
225kVA / 180kW
300kVA / 270kW
375kVA / 338kW
500kVA / 450kW
750kVA / 675kW
480V
480V
480V
480V
480V
480V
480V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
TABLE 1.4
UPS Module Information
UPS
[kVA]
Cable
Entry
Width
[in / mm]
Depth
[in / mm]
Height
[in / mm]
Weight
[lb./ kg]
Heating
[kBTH / h]
100
BOTTOM
43.3 / 1100
29.8 / 758
79.7 / 2025
2061 /
935
19
150
BOTTOM
47.2 / 1200
29.8 / 758
79.7 / 2025
2579 / 1170
28
225
BOTTOM
55.1 / 1400
29.8 / 758
79.7 / 2025
3263 / 1480
43
300
TOP
76.8 / 1950
37.7 / 958
79.7 / 2025
4564 / 2070
59
375
TOP
76.8 / 1950
37.7 / 958
79.7 / 2025
4916 / 2230
73
500
TOP
114.2 / 2900
37.7 / 958
79.7 / 2025
6923 / 3140
89
750
TOP
129.9 / 3300
49.5 / 1258
79.7 / 2025
9193 / 4170
134