MITSUBISHI ELECTRIC 9800A SERIES UPS
MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-14
Description of Figures 1.4, 1.5, and 1.6:
1.
CPM
- Circuit protector for control power supply.
2.
Grounding bar (G)
3.
External contact signal terminal block
(FIGURE 1.6)
-
Terminal block to connect
contact signal input/output lines to and from the external devices. Refer to Figure 2.15
section 2.4 for details.
4.
RS232C communication connector
(FIGURE 1.6)
-
Refer to Figure 2.18 section 2.5 for
details.
5.
Inverter start switch -
This switch is used to transfer the UPS from static bypass to
inverter during maintenance purposes. Transfers will lock-out if the bypass voltage is
more than +12%,-12% of nominal.
* Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at
the time of asynchronous operation.
6.
“INVERTER STOP” switch
- This switch is used to transfer the UPS from inverter to
static bypass during maintenance purposes. Do not operate it under normal operation.
Transfers will lock-out if the bypass voltage is more than +12%,-12% of nominal.
* Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at
the time of asynchronous operation.
7.
“FAULT RESET” switch (FOR SERVICE PERSONNEL ONLY) -
This switch resets
errors resulting from alarm conditions. (Do not operate this switch while inverter and
converter are in operation.)
8.
Maintenance (Set) button (FOR SERVICE PERSONNEL ONLY) -
This switch sets the
UPS menu parameters.
9.
“Test mode” switch (FOR SERVICE PERSONNEL ONLY) -
This switch changes
system operation to the test-mode.
(This switch should not be operated by personnel
other than an Authorized Service Engineer).
10.
“BOOT” switch (FOR SERVICE PERSONNEL ONLY)
- This switch boots the
processor in the main control circuit resulting from alarm conditions.
(Do not operate
this switch while inverter and converter are in operation).