Setting the Supply Voltage
1. With the 3-phase electrical enclosure door open, restore power to the machine.
2. Look at the VFD screen through the viewer slot in the door for errors.
If
Fault 5093
appears on the VFD screen, cycle the power again to clear the fault.
3. If the VFD displays
Warning A6A6
, perform these steps to set the correct supply
voltage:
a) Press the Left Selector to
select
Hide,
and the
display will change
screens
.
b) Choose
Select
Parameter.
c) Arrow to
95
and select it.
d) Arrow to
01
and select it.
e) Arrow to the appropriate
voltage according to
Table 1 and select it.
f) Press
Back
until you
reach
Exit
, and select it.
4. Close all enclosure doors.
!
WARNING
ELECTROCUTION HAZARD.
All components have electrical power during these next steps.
All electrical work must be performed by a qualified electrician.
If it is absolutely necessary to troubleshoot an energized
machine, follow NFPA 70E for proper procedures and person
protective equipment.
Left
Selector
Figure 9: VFD Interface
Table 1: Supply Voltage Settings
Machine
Voltage
Supply Voltage
Setting
208
208-240
230
208-240
415
380-415
460
500
575
525-600