Garden/Tower-MICRO Use and installation manual Page 15 of 20
Technical specifications and connections
Parametro
Valore
Lobo dimensions:
-
height
-
opening
max 2,50 m
max 1,0 m
Operating temperature
da -40°C a +65°C
DZ length
da 1 a 200 m
Range of detection speeds
da 0,1 a 10,0 m/s
Range of working supply voltage
da 12 a 36 Vdc
Maximum current required at the working supply voltage of 24V
-
TX
-
RX
80 mA
100 mA
Maximum recovery time of the stand-by system after notification of an alarm
10 s
Parameters of signal, switched with the contacts of the output circuit:
-
maximum current, constant or alternate
-
maximum voltage
30 mA
72 V
Minimum signal duration
5 s
Operating frequency
da 24.00 a 24.25 GHz
C
C
C
Connections
onnections
onnections
onnections
After fixing the base (see the installation options on p. 6 and how to fix the column to the base
on p. 8 of the manual) and powering the column (see page 15), follow the following
instructions:
1. carry out the manual adjustment of the device by rotating the TU and RU units in the
desired direction till the alarm signal switches off.
To carry out the adjustment, loosen the fixing screws of the TU and RU units.
Take care, the rotations must be slow and gradual.
Never rotate violently.
2. Once the adjustment has been completed, tighten the fixing screws of the TU and RU
units.