Trial run
Before trial run
After installation, and piping and cable connection, of both the indoor and outdoor units is complete,
check the following items:
• Refrigerant leaks
• Power supply complies with requirements.
• Control cables and power cord have been installed correctly.
Function test
Switch on the appliance after the checking.
If a “beep” is heard, it basically means the unit works normally, otherwise check it again.
(Since the front panel has not been installed, it can not be checked through the indicators and remote controller yet.)
• Remove the cover for checking and add some water(about 2000ml) in through a funnel;
• Normally, the fl oater switch can be seen fl oating from the viewing window, and the water pump
starts to drain, which can be seen through the transparent drain port.
• If not, check the electrical system of the unit again.
Only after adjustment of levelness and drain system of the unit, do the following:
Front panel installation
Remove 4 corner panels from the air inlet grill of front panel as shown above;