V 19.01
15
English
3.
Use
3.9
Change the duration between automatic spool cycles
The spool function is used to prevent the formation of legionella and other waterborne
pathogenic microorganisms in the water system. The system will automatically spool
itself with water after a certain amount of time the system has not dispensed water
while connected to a power supply. While spooling, the system automatically passes
step by step the entire temperature field beginning with cold water and ending with hot
water.
Press «SPOOL» button. The water sector will light up. With the «+» and «-» buttons
on the remote control, the duration of time between spool cycles can be changed. To
save settings, press the «SAVE» button. All colored LED lights illuminate to indicate
new setting has been saved. If «SAVE» button is not pressed within 10 seconds of last
selection, previously saved setting will be stored.
There are 9 settings available. Each setting is indicated with a different beep tone. For
models with a display screen, this will also be indicated visually on screen. Please see
Fig. C - E for technical data.
3.10
Change duration of automatic spool cycle
During the spool cycle, water will automatically dispense for a certain amount of time
referred to as the DURATION on the remote control. While spooling, the system auto-
matically passes step by step the entire temperature field beginning with cold water and
ending with hot water.
Press the «DURATION» button. The water sector will light up. With the «+» and «-»
buttons, the duration of continuous water flow in spool mode can be changed. To save
settings, press the «SAVE» button. All colored LED lights illuminate to indicate new
setting has been saved. If «SAVE» button is not pressed within 10 seconds of last
selection, previously saved setting will be stored.
There are 9 settings available. Each setting is indicated with a different beep tone. For
miscea models with a display screen, this will also be indicated visually on screen.
Please see Fig. C - E for technical data.
3.11
Change the system light settings
The lights in the head of the miscea faucet can be put into the following 3 modes: on,
pulse and off.
Press the «LIGHT» button. Use the «+» and «-» buttons to switch between different
light modes. To save settings, press the «SAVE» button. All colored LED lights illumi-
nate to indicate new setting has been saved. If «SAVE» button is not pressed within 10
seconds of last selection, previously saved setting will be stored.
Please see Fig. C - E for technical data.
SPOOL
DURATION