Installing the NC-220 ZF3
The input terminals for the ZF3 are TS1 (cancel button) and TS2 (2 generic inputs). They are
located on the ZF3 circuit board (see Figure 30). To connect an input, attach the positive and
negative wires from the input to the input and ground terminals on either TS1 or TS2.
Figure 30 Input terminals TS1 and TS2 on the NC-220 ZF3.
6.3 Power
To power the ZF3, insert a CR123A battery in the battery terminal, BT1, located on the ZF3
circuit board (see Figure 30).
6.4 Mounting the ZF3
The ZF3 mounts on a wall using four screws. After mounting the ZF3, attach the cover plate to
the unit.
Note that the ZF3 is not intended to be used in an Oxygen-Enriched Environment.
6.5 Maintenance and Service
Mircom recommends that each ZF3 be tested on a weekly basis.
When performing service on a ZF3, remove its battery and then disconnect any input
connections before accessing any serviceable areas.
Note:
Prior to mounting the ZF3, record its MAC address and location (building, wing,
floor, and room). This information is needed to add the ZF3 to the MiCare Central
server. Appendix 5: Device Installation Table on page 60 has an example device
installation table that you can use to record this information.
Attention: The ZF3 is not to be installed in a shower stall or in an equivalent
location where water spray would be encountered.
TS1
TS2
BT1
CR123A
CANCEL
1 2
INPUT 1
INPUT 2
GND 1
GND 2
GND
INPUT
i
!