34
LED Indication
The Alarm Zone LED indicator flashes when one sample indicates an alarm condition. If the
alarm is confirmed the LED indicator will illuminate steady. If 15 seconds elapses without any
samples in the alarm condition the LED Indicator will turn OFF. The waterflow retard operation
operates regardless of whether or not the system is in alarm.
5.2.9
System Status Correlations
The following System Status processes can be correlated to configured (mini) monitor
modules:
•
System Reset
•
Fire Drill
•
Acknowledge
•
Total Evacuation
•
Buzzer Silence
•
Signal Silence
•
Acknowledge General Alarm
•
Auxiliary Disconnect
5.2.10
Audible Walktest
Configures (mini) monitor modules as audible when conducting a walktest. For more
information on performing a walktest see 5.11.6 Walk Test.
5.2.11
Silent Test
Configures (mini) monitor modules as silent when conducting a walktest. For more information
on performing a walktest see 5.11.6 Walk Test.
5.2.12
Manual Day/Night
Configures (mini) monitor modules for manual day/night alarm thresholds. For more
information on alarm thresholds see 5.1.3 Alarm Conditions.
5.2.13
Auto Day/Night
Configures (mini) monitor modules for auto day/night alarm thresholds. For more information
on alarm thresholds see 5.1.3 Alarm Conditions.
5.2.14
Verified Alarm Input
Un-bypassed verified alarm inputs entering into alarm are verified over a period of time to
determine if the alarm condition is valid.
Note:
Do not use the retard operation with any external retarding device.
Attention: Devices correlated with any of the above System Statuses need to be
contained within a secured enclosure accessibly only to those with the
proper authority.