FX-350 Series Installation and Operation Manual
43
Evacuation Codes
Single stage codes
Two-stage codes
:
Figure 19: Evacuation and Alert Codes
Initial Power-up Sequence
When the system powers up, it performs an initial self diagnostic and executes a system reset to reset all external
devices. The common trouble sequence is then initiated. The system must be reset manually to clear the trouble.
At power-up, a check is performed on the configuration data, program, and RAM memory. If an error is found, the
system is placed in trouble but the system attempts to continue to operate.
The power-up sequence will occur when power is first applied to the panel, when power is restored after a total
power failure (including battery power), or when the watchdog timer expires. It is also implicitly executed when the
system comes out of configuration mode after auto-configure or a new configuration has been downloaded from the
configurator.
The power-up complete status is set to indicate that the system power-up is complete and the system is in normal
operating mode.
Shared Display
The shared display consist of a 2 line by 20 characters LCD and alpha numeric keys. It operates in three basic
modes: status display mode, queue display mode and command mode. Status display mode displays system
activity when the queues are empty. When there are items in the queues, queue display mode is used to browse
the status of all active points in the queues. Command mode which allows the user to execute certain commands,
performs certain system test and front panel configuration of the system.
Continuous
On 100% of the time
Temporal Code
3 of 0.5 second ON, 0.5 second OFF then, 1.5 second pause
March Code
0.5 second ON, 0.5 second OFF
California Code
5 seconds ON, 10 seconds OFF
Alert Code
0.5 second ON, 2.5 seconds OFF
General Alarm
Evacuation code as selected from Figure18 below.
0.5s
0.5s
1.5s
0.5s
0.5s
5s
10s
CONTINOUS
TEMPORAL CODE
MARCH CODE
CALIFORNIA CODE
0.5s
0.5s
1.5s
0.5s
0.5s
5s
10s
CONTINOUS
TEMPORAL CODE
MARCH CODE
CALIFORNIA CODE
10s
2.5 s
ALERT CODE