Indicators, Controls and Operations
42
Output Types
Output Type
Description
Signal
This output type is for audible devices such as bells and piezo mini-horns. Signals operate in
alert (two stage) and/or evacuation rate.
Strobe
Normal (non-sync)
:
Strobe circuits operate similar to signals except that they are always turned ON continuously
(they are not affected by the alert or evacuation rates) if configured as normal. When
configured as normal the output circuit does not use any sync protocol. Normal strobes can
be silenceable or non-silenceable.
Synchronized:
Output circuits configured as strobes can have sync protocol for synchronization. When the
output circuit is configured as strobe and also configured as non-silenceable and the device
used on the output is a combination of horn and strobe, then if the signal silence is activated
while the circuit is active the horn(s) are silenced while the strobe keeps on flashing.
Synchronized strobes and strobe/horn models of the following manufacturers are supported:
Faraday, System Sensor, Wheelock, Gentex, and Mircom.
Relay
Un-bypassed relay outputs are activated if any un-bypassed input circuit or common system
status which has been programmed to it is active. If the relay is configured as "silenceable" it
is inhibited when common auxiliary disconnect is active. Relays also turned off if they are
bypassed or if all inputs and system status correlated to it are restored or bypassed.
Note:
Silencing of the horn depends on the feature provided by the manufacturer of the horn/strobe
combination. Some models of the horn/strobe combination may not have this feature and will not
work as described above.