BPS-1100 Installation and Operation Manual
27
10.7 Configuring Features
There are two types of Features; those which are just turned ON and OFF, and those with Multiple Settings. For ON
and OFF Features, the Select LED is lit for ON, and not lit for OFF, and the Select Button is pressed to change the
ON / OFF setting. For Multiple Setting Features, the Select LED flashes a number of times to indicate the setting,
then pauses; the Select Button is used to change the selected setting. Be sure to pause for about 3 seconds after
changing the Configuration DIP Switches, or pressing the Select Button to see the results.
Table 4: Feature Configuration Dip Switch Table
Dip Switch Position
(1-8)
Feature
Description
O000 0100
Two Stage Operation Enabled
Select LED lit indicates that the System is set for Two
Stage which means the normal alarm will activate the
outputs at the Alert Rate and the general alarm will
activate the outputs at the Evac rate.
0000 0110
Output Circuit Correlations
Enabled
Select LED lit indicates that Output Circuits (Indicating
Circuits and Relays) operate according to any set
Correlations (see Correlation section). If the Select LED
is not lit (default), all Output Circuits are Common
Alarm; all outputs turn on for any Alarm Input.
0001 0010
Signal Circuit Isolator Option
Select LED lit indicates that if there exists a short circuit
on any Indicating Circuit and an alarm condition follows,
then those Indicating Circuits will be activated anyway. If
Select LED is not lit (default), then under same
conditions, the Indicating Circuits will not be activated to
prevent wasting power. This feature is needed when
Signal Isolator Devices are employed so that Indicating
Circuits will be activated even under shorted conditions.
0011 1000
Show Relay Circuits
All Display Points assigned to Relay Circuits will be lit.
0000 1101
Audible Indicating Circuit
Evacuation Code
Select LED flashes 1 time = Continuous
Select LED flashes 2 times = March Time
Select LED flashes 3 times = Temporal Code (default)
Select LED flashes 4 times = California Code