 LT-6010 Rev 1  June 2010

BBX-2000 
Integrated Fire/Audio Cabinet

Mechanical Installation

The Integrated Fire/Audio Cabinet is the network fire alarm and audio floor or node panel.  It is mounted into the BBX-
2000 backbox and door.  Mount the backbox onto the wall using six #8 screws to secure the backbox to the wall.  The 
backbox is surface mounted only; the dimensions for the mounting holes are shown in Figure 1 below.  The 
Integrated Fire/Audio Cabinet consists of the Audio Card Cage, FX-2000ND Deep Chassis with FX-2000N Main 
Control board/2 Amp Battery Charger, and PS-2040 10 Amp Fire Alarm/30 Amp Audio Power Supply. Batteries are 
mounted in the tray located at the bottom of the enclosure.

Figure 1: BBX-2000 Enclosure with the Integrated Fire and Audio System

16.5”

16.5”

 25”

 25”

 33.5”

 33.5”

BBX-2000 Enclosure

QMB-5000N Audio Card Cage

FX-2000ND Main Chassis with 
provision to mount FNC-2000
Network Controller Module and
2 adder modules/loop controllers

PS-2040 Power Supply and space 
to mount 6 adder modules/
loop controllers

Batteries (maximum 40 AH)

Metal plate with ANC-5000 and 
TNC-5000 modules aboard fit 
into position 1 of the QMB-
5000N Audio Card Cage

QAA Amplifiers fit 
into slot positions 2, 
3, 4 and 5. 