Important!

 The shower circuit should be separated from other circuits by at least

twice the diameter of the cable or conduit and it should not be run through thermally
insulating material or in locations where the ambient temperature is likely to
exceed 30 °C. If any of these conditions are unavoidable it is necessary to perform
the full calculations detailed in BS7671 to determine the cable size. This will
prevent damage to the cable caused by overheating.

2.4.

To obtain full advantage of the power provided by this unit, use the shortest
possible cable route from the consumer unit to the shower. It is also necessary
to satisfy the disconnection time and thermal constraints which mean that, for any
given combination of current demand, voltage drop and cable size, there is a
maximum permissible length of circuit.

As a guide only, 

the following maximum permissible lengths are given for 6 mm

2

cable protected by a 40A MCB type B and allowing for a 5 Volt drop:

Sprint 7.5 kW (240 V AC) at 240 V -

22 Metres

Sprint 8.5 kW (240 V AC) at 240 V -

19 Metres

Sprint 9.5 kW (240 V AC) at 240 V -

18 Metres

2.5.

A 30 mA residual current device (RCD) should be fitted. This may be part of the
consumer unit or a separate unit.

2.6.

A separate, permanently connected supply must be taken from the consumer unit
to the Mira Sprint through a double-pole switch, which has at least
3 mm contact separation. The switch can be a ceiling mounted pull-cord type within
the shower room or a wall mounted switch in an adjacent room.

2.7. DO NOT

 twist the individual cable cores of the live and neutral conductors, as this

will prevent them from entering the terminal block.

2.8. DO NOT

 exert strain on the terminal block.

2.9. DO NOT

 turn-on the electrical supply until the plumbing has been completed.

Power

Low Flow

Temperature

Stop Start

Plumbing and Electrical Schematic Diagram

Содержание Sprint 7.5

Страница 1: ...1 Maintenance Guide Operation B Installation ELECTRIC SHOWERS THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER 7 5 8 5 and 9 5 kW Power Low Flow Temperature Stop Start...

Страница 2: ...Contents Checklist 7 4 Dimensions 8 5 Wiring Diagram 9 6 Specifications 10 7 Installation Requirements 10 8 Installation 14 9 Commissioning 17 10 Operation 19 11 Maintenance 23 12 Fault Diagnosis 28 1...

Страница 3: ...dset with three different spray actions start force and soothe Individual lights indicate POWER and LOW FLOW Supplied complete with flexible hose adjustable clamp bracket assembly slide bar and suppor...

Страница 4: ...stnotbefittedwhereitmaybeexposedtofreezing conditions 1 7 If water leaks from the pressure relief valve maintenance will be required before the Mira Sprint can be safely used 1 8 DO NOT fit any form o...

Страница 5: ...of these instructions and retain this guide for later use 2 2 Pass on this guide in the event of change of ownership of the installation site 2 3 Follow all warnings cautions and instructions containe...

Страница 6: ...ng Particular consideration should be given to the young the elderly the infirm or anyone inexperienced in the correct operation of the controls 2 8 When this Mira Sprint has reached the end of its se...

Страница 7: ...o confirm that the parts are included 2 Documentation 1 x Installation Operation and Maintenance Guide 1 x Installation Template 1 x Customer Support Brochure Section 3 Pack Contents Checklist 1 Mira...

Страница 8: ...8 Power Low Flow Temperature Stop Start Section 4 Dimensions 203 5 mm 342 mm 79 mm...

Страница 9: ...ion Load P E N Solenoid Valve Pressure Power Selector Switch Low Flow Neon Inlet Connector Wiring Diagram Section 5 Power On Neon 92 Green 91 Green 90 Blue 89 Brown 96 Red 97 Brown 99 Brown 93 Black 9...

Страница 10: ...bar up to a maximum static inlet pressure of 10 bar 1 2 The Mira Sprint is normally connected to the cold water mains fed supply However thewatersupplycanbetakenfromacoldwaterstoragecistern provided...

Страница 11: ...e when soldered fittings are used pre solder the pipework and fittings before connecting them to the inlet connector assembly 1 10 TheMiraSprintisfittedwitha BSPmaleoutletthread toacceptaMirashower ho...

Страница 12: ...he Mira Sprint Voltage drop due to local heavy demand will reduce the shower s performance 2 2 TheMiraSprint mustbeearthedbyconnectingthesupply cableearthconductor to the earth terminal Supplementary...

Страница 13: ...guide only the following maximum permissible lengths are given for 6 mm2 cable protected by a 40A MCB type B and allowing for a 5 Volt drop Sprint 7 5 kW 240 V AC at 240 V 22 Metres Sprint 8 5 kW 240...

Страница 14: ...vice tunnel 1 5 Determine the direction of the inlet water supply top falling bottom rising or back inlet Note Make sure that the back inlet does not go directly back into the wall Use a soldered elbo...

Страница 15: ...Connector Assembly Cold Water Supply Pipe Terminal Block Cover Retaining Screw Holes For Cover Retaining Screws The inlet connector assembly can be swivelled to suit the supply Do not fit the Mira Spr...

Страница 16: ...Connect the conductors firmly into the terminal block Make sure that the bare cores of each conductor are securely trapped within each conductor clamp L Red wire N Black wire E Yellow Green sleeved wi...

Страница 17: ...to the low position 1 5 Switch on the electrical supply at the double pole switch The POWER neon will provide a visual indication that the electrical supply is connected 1 6 Press the START button Che...

Страница 18: ...he TOP knob to the medium position The temperature of the water should rise slightly Allow a few seconds for the warm water to reach the handset this shows that the MEDIUM power setting is operatingco...

Страница 19: ...re of the incoming cold water supply and or fluctuationsinmainselectricalvoltage willrequirethe TEMPERATURE knobto be adjusted as necessary 1 5 The Mira Sprint requires a minimum maintained running pr...

Страница 20: ...rise Showering temperature minus the incoming cold water temperature Example For the Mira Sprint 7 5 kW on full power setting with an incoming water supply at10 Candashoweringtemperatureat45 C thetemp...

Страница 21: ...handset 2 5 IfnecessaryturntheBOTTOMcontrolknobslowlytoadjusttemperature Allow 10 15 seconds for the adjusted temperature to reach the handset The control knob operates through approximately of a tur...

Страница 22: ...22 COLD Power Low Flow Temperature Stop Start Stop Start Hotter Cooler High Medium Low Press to Start Stop...

Страница 23: ...ce Only a competent tradesperson should remove the cover 3 Flow Valve and Switch Assembly Removal and Installation WARNING Isolate the electrical and water supplies before removing the cover Mains ele...

Страница 24: ...lenoid wires 3 11 Remove the flow valve and switch assembly 3 12 Refit the components in reverse order Make sure that the electrical wires are installed in the correct positions Flow Valve and Switch...

Страница 25: ...sition 4 6 Carefully pull the flow valve and switch assembly and the heater tank away from thecase Makesurethatyoueasetheinletconnectorassemblyofftheinletsupply pipe 4 7 Make a note of the positions o...

Страница 26: ...ions 5 Thermal Switch Removal and Installation WARNING Isolate the electrical and water supplies before removing the cover Mains electricity connections are exposed when the cover is removed 5 1 Remov...

Страница 27: ...ctrical wires are installed in the correct positions 6 Inlet Filter Replacement WARNING Isolate the electrical and water supplies before removing the cover Mains electricity connections are exposed wh...

Страница 28: ...ction Cause Remedy No water or very low flow rate Handset sprayplate blocked Remove clean Refer to Maintenance in the I O M guide for the fittings Incoming water supply stop valves or appliance isolat...

Страница 29: ...ming water supply stopcock and or appliance isolating valve turned fully on If fault still persists contact your installer Unable to select a cool enough shower during summer months Due to the rise in...

Страница 30: ...41649 Low Flow Neon Assembly 41650 Power On Neon Assembly 41651 SolenoidCoil 41652 OutletConnector 41749 Terminal Block Assembly7 5 8 5kW 41750 Flow Valve Assembly 41751 Switching Assembly 41921 Heate...

Страница 31: ...w Temperature Stop Start 2 Mira Sprint Spare Parts Diagram 416 41 419 23 419 22 419 21 416 43 419 27 416 48 416 51 417 50 872 01 416 49 416 50 416 38 872 28 416 47 419 28 417 49 419 25 416 52 A A A B...

Страница 32: ...BS EN ISO 9001 1994 Reg No FM 14648 Mira is a registered trade mark of subsidiaries of Caradon Mira Limited Thecompanyreservestherighttoalterproduct specifications without notice Guarantee Caradon Pl...

Отзывы: