3.4. Connecting the Equipment
Plug the equipment into the output receptacles on the PDU. Do not use extension
cords, adapter plugs or surge strips on the output of the PDU. Ensure that the load
does not exceed the maximum output rating of the PDU (refer to the information label
on the PDU or the Electrical Specifications in this manual).
3.5. Connecting to the Power Source
1. Verify that the voltage and frequency ratings match that of the Utility power, and
then connect the AC Input power cord into a two-pole, three -wire grounded
receptacle only. The receptacle shall be installed near to the PDU and shall be
easily accessible. Do not use extension cords, adapter plugs, or surge strips.
The PDU has an external ground stud for attaching an external ground wire from
the rack to the PDU.
NOTE: Each individual input power cord for the dual circuit PDU
(MMPD2020V60DCL) must be connected to its own Branch Circuit.
2. Turn the Power Switch to the on position (Not on all models).
3. The Power On LED (green) will illuminate indicating that the PDU is on and
providing power to the connected equipment (Not on all models).
4. The Surge LED (green) will illuminate indicating that the PDU is on and providing
surge protection to the connected equipment (Not on all models).
5. Turn on the connected equipment.
6. The installation is complete the PDU is ready for normal operation.
Chapter Four: Troubleshooting
If the PDU malfunctions, check the list below to resolve the problem. Should the
problem persist, call for service.
Situation Check
Items
Solution
Power On LED is not on
and there is no output
power.
1.Input power cord not
plugged in to the wall outlet.
2.Input circuit breaker is
tripped.
3.The circuit breaker at the
service panel is tripped.
4.No Utility power available.
1.Connect the Input power
cord to the wall outlet.
2.Unplug the input power cord
and reset the input circuit
breaker. Connect the Input
power cord to the wall outlet.
3.Unplug the input power cord
and reset the circuit breaker
at the service panel.
Connect the Input power cord
to the wall outlet.
4.Contact your local Utility
company.
The Power On LED is off,
but there is output power.
There is an internal fault, call
for Service.
One of the connect
equipment does not turn
on.
With a voltmeter, check the
output receptacle for an AC
voltage.
1.If there is an AC voltage at
the output receptacle, check
the connected equipment.
2.If there is not an AC voltage
at the output receptacle, there
is an internal fault, call for
Service.
The Surge Protection LED
is off.
The surge protection devices
are blown, call for Service.
En
g
lish
7
Appendix
A.1. Specifications
Model Number
MMPD2020V60DCL
Maximum Load Capacity
16Amps per circuit
INPUT PARAMETERS
Number of Phases
Single (1
∅
2W +G)
Nominal Voltage
120VAC
Frequency 50/60Hz
Input Protection
Re-settable circuit breakers (2)
OUTPUT PARAMETERS
Nominal Voltage
120VAC
Frequency 50/60Hz
Branch Circuit Protection
UL 60950-1
Circuit Quantity
2 (16Amp circuits)
ENVIRONMENTAL
Operating Temperature
+32
°
- +104
°
F (0
°
- 40
°
C)
Storage Temperature
+32
°
- +149
°
F (0
°
- 65
°
C)
Operating/Storage Humidity
0 - 90%, non-condensing
Operating Elevation
0 to 3,000m (0 to +10,000 ft)
Storage Elevation
0 to 15,000m (0 to +50,000 ft)
PHYSICAL
Input Power Cords
15-feet (2)
Input Plugs
NEMA L5-20P (2)
Output Receptacles
20-Total (10 per circuit)
NEMA 5-15/20R
Mounting Format
Vertical (Zero U)
Net Dimension
(L x W x H)
60.0 x 1.64 x 1.50”
(1524.0 x 41.4 x 38.1 mm)
Net Weight
Lbs (Kgs)
8.16
(3.70)
Ship Dimensions
(L x W x H)
63.27 x 4.80 x 3.07”
(1607 x 122 x 78 mm)
Ship Weight
Lbs (Kgs)
9.0
(3.87)
REGULATORY COMPLIANCE
Safety/Approvals
UL 60950-1, cUL (CSA 22.2), CE
En
g