background image

15

14

TURNING OFF THE STEP DOWN TRANSFORMER IN THE NORMAL AC
MODE:

1. Press and release the On/Off/Test Button on the front panel of the UPS aft-

er the second beep to transfer the UPS to the Bypass mode.

2. Turn off all of the connected equipment.
3. Turn off all of the Load breakers on the rear panel of the ED-XFR.
4. Turn off the input breaker on the rear panel of the UPS.
5. Turn off the DC breaker(s) on the rear panel of the Battery Pack(s).

TURNING OFF THE STEP DOWN TRANSFORMER IN THE BATTERY
MODE:

1. Turn off all of the connected equipment.
2. Turn off all of the Load breakers on the rear panel of the ED-XFR.
3. Press and release the On/Off/Test Button after the second beep to turn the

UPS off.

4. Turn off the input breaker on the rear panel of the UPS.
5. Turn off the DC breaker(s) on the rear panel of the Battery Pack(s).

START-UP IN THE BATTERY MODE:

The Battery Pack(s) must be connected to the UPS and the DC breaker(s) on
the rear panel of the Battery Pack(s) must be in the on position.  The input of
the ED-XFR must be connected to the output of the UPS. The equipment must
be plugged into the output receptacles on the ED-XFR.
1. Turn on the input breaker on the rear panel of the UPS.
2. Press and release the On/Off/Test Button after the first beep to turn the

UPS on.

3. The fans will turn on, then the UPS will start-up and perform a self-diagno-

sis for approximately 10-seconds.

4. Turn on all of the Load breakers on the rear panel of the ED-XFR.
5. Turn on the connected equipment one at a time.  See the UPS user's ma-

nual for more information.

1. Turn on the input breaker on the rear panel of the UPS.  The fans will turn

on, the AC normal icon will flash off/on and the LCD will display ‘bPS’.  The
UPS is now in the Bypass mode.  

NOTE:

  If there is a power interruption

while the UPS is in the Bypass mode the load will not be backed up.

2. Turn on all of the Load breakers on the rear panel of the ED-XFR.
3. Turn on the connected equipment one at a time.
4. Press and release the On/Off/Test Button after the first beep to turn the

UPS on.

5. The UPS will start-up and perform a self-diagnosis for approximately 10-

seconds.  The UPS system is ready for normal opeartion.  See the UPS
user's manual for more information.

120V outputs:
La - N:  50A max, Lb - N:  50A max, the combined total for both:  83.4A max
208V output:  Lc - Ld:  48.1A max
240V output:  La - Lb:  41.7A max

NOTE:  

Default voltages for the output receptacles are 120V and 208V.  240V is

available, but only as a hardwire option at the output terminal block.

Chapter 4: Operation

START-UP IN THE NORMAL AC MODE:

The UPS must be connected to utility power and there must be an acceptable AC
voltage present.   The Battery Pack(s) must be connected to the UPS and the DC
breaker(s) on the rear panel of the Battery Pack(s) must be in the on position.  The
input of the ED-XFR must be connected to the output of the UPS.  The equipment is
plugged into the output receptacles on the ED-XFR.

c)

Connect the green wire labeled G on the input power cable to the ED-
XFR AC input terminal block ground terminal and secure.

2. Connect the other end of the #6 AWG input power cable labeled "TO UPS" to

the output terminal block on the UPS and secure.
a)

Connect the black wire labeled L on the input power cable to the UPS out-
put terminal block labeled L and secure.

b)

Connect the white wire labeled N on the input power cable to the UPS out-
put terminal block labeled N and secure.

c)

Connect the green wire labeled G on the input power cable to the UPS out-
put terminal block ground terminal and secure.

3. Re-install the terminal block cover plate on the ED-XFR.
4. Before re-installing the terminal block cover box on the UPS, see the UPS us-

ers manual for the UPS input and output connections.

5. Plug the equipment into the output receptacles on the rear panel of the ED-

XFR. The ED8000RT-XFR and ED10000RT-XFR have a terminal block for ha-
rdwiring the output. Refer to the figure below for the input / output connections.
The pins for the output cable are included.

NOTE:

  The two 120V outputs are individual 5KVA outputs and they 

CANNOT

 be

paralleled.

Input / Output terminal block for the ED8000RT-XFR and ED10000RT-XFR:

Содержание ED10000R T-XFR

Страница 1: ... s Manual Endeavor 5 10KVA Step Down Transformer Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000473 R2 ...

Страница 2: ...1 1 Introduction 2 2 Rear Panels 6 3 Installation 8 4 Operation 14 5 Obtaining Service 16 6 Specifications 17 7 Limited Product Warranty 18 A1 Declaration of Conformity 19 Table Of Contents ...

Страница 3: ... equipment the user must ensure that the ED XFR is properly grounded due to a possible risk of AC current leakage CAUTION This ED XFR series is ONLY intended to be installed in an indoor temperature controlled environment that is free of conductive contaminants This ED XFR series is not intended for use in a computer room as defined in the Standard for the Protection of Electronic Computer Data Pr...

Страница 4: ...e reasonable protection against such interference in a residential installation This equip ment generates and uses radio frequency and if not installed and used properly that is in strict accordance with the manufacturer s instructions this equip ment may cause interference to radio and television reception If this equip ment does cause interference to radio or television reception which can be de...

Страница 5: ...rheated 12 Input voltage selection switch 208 240V The default setting is 208V 1 The Load 4 circuit breaker will trip in the event the load exceeds the power rating 2 Load 4 120V output receptacles 4 5 15 20R 3 The Load 2 circuit breaker will trip in the event the load exceeds the power rating 4 Load 2 120V output receptacles 4 5 15 20R 5 The Load 2 circuit breaker will trip in the event the load ...

Страница 6: ...nt Configuration to install the unit into the rack USE CAUTION The ED XFR UPS and Battery Pack are extremely heavy Use the appropriate number of personnel when installing the UPS system CAUTION DO NOT USE THE MOUNTING BRACKETS TO LIFT THE STEP DOWN TRANSFORMER The mounting brackets are ONLY for securing the unit to the rack Chapter 3 Installation RACKMOUNT CONFIGURATION Use the included rackmount ...

Страница 7: ...ing of these ED XFR 1 Before connecting to the input output terminals read all of the Cautions and Warning then observe the following a Ensure that the UPS is turned off and not connected to the AC sour ce or the battery source before any connections are made b Calculate the power consumption of the load to ensure that an over load condition does not occur c Ensure that the terminal block screws a...

Страница 8: ...rear panel of the ED XFR to the appropr iate voltage 208V 240V NOTE The default setting is 208V The ED XFR s input voltage setting must be the same as the UPS s output voltage set ting 6 Plug the equipment into the output receptacles on the rear panel of the ED XFR NOTE Default voltages for the output receptacles are 120V and 208V Load 2 ouput receptacle can be changed to supply 240V but this chan...

Страница 9: ...nd release the On Off Test Button after the first beep to turn the UPS on 5 The UPS will start up and perform a self diagnosis for approximately 10 seconds The UPS system is ready for normal opeartion See the UPS user s manual for more information 120V outputs La N 50A max Lb N 50A max the combined total for both 83 4A max 208V output Lc Ld 48 1A max 240V output La Lb 41 7A max NOTE Default voltag...

Страница 10: ... tripped circuit breakers A tripped circuit breaker is the most common issue 3 Call your dealer for assistance If you cannot reach your dealer or if they cannot resolve the issue call or fax the Technical Support department at the following numbers Voice phone 972 446 7363 FAX line 972 446 9011 or visit our Web site at www minutemanups com the Discussion Board Before calling the Technical Support ...

Страница 11: ...the equipment is damaged by the customer is improp erly used is subjected to an adverse operating environment or is operated outside the limits of its electrical specifications b the equipment is repaired or modified by anyone other than Para Systems or Para Systems approved personnel or c has been used in a manner contrary to the product s User s Manual or other written instructions Any technical...

Страница 12: ...21 20 Notes Notes ...

Отзывы: