Chapter 6:  Specifications

Waveform Type

True Sine Wave

>95% (Full Load)

50 / 60Hz

208VAC - 49Amps
240VAC - 42.5Amps

208 & 120VAC (Default) / 240VAC (Optional)

Efficiency

Voltage (Selectable)

Frequency

Model Number

SYSTEM SPECIFICATIONS

Current (Max)

Topology

Isolation, Step Down Tansformer, Sine Wave

OUTPUT

INPUT

Number of Phase

Single (1

 

2W +G)

Voltage (Selectable)

208 (default) / 240VAC

Protection

Resettable Circuit Breaker

Voltage Regulation

N/-3%

Frequency

50 / 60Hz

Protection

Resettable Circuit Breaker

208VAC - 24Amps
240VAC - 21Amps

Audible Noise at 1 m (3 ft.)

ENVIRONMENTAL

Operating Temperature (max)

Operating/Storage Humidity

Operating Elevation

0 to 40

°

C (+32 to +104

°

F)

0 ~ 95% Non-Condensing

0 to 2,000m (0 to +6,562 ft)

PHYSICAL

Weight - Net

Size - Net
L X W X H

Size - Shipping
L X W X H
Weight - Shipping

82.7 lbs / 35.5 Kgs

158.7 lbs / 72.0 Kgs

123.5 lbs / 56.0 Kgs

196.2 lbs / 89.0 Kgs

REGULATORY COMPLIANCE

Safety and Approvals

EMC Verification

cTUVus

(Conforms to UL60950-1:2007 R12.11, CSA-C22.2 No.60950-1-07-A1:2011)

FCC Class B, CE certified

Storage Elevation

0 to 15,000m (0 to +49,213 ft)

Storage Temperature

-15 to +50

°

C (+5 to +122

°

F)

<60 dBA

26.2 x 17.3 x 3.5"
665 x 440 x 88.5 mm

31.6 x 24.4 x 9.1"
802 x 620 x 230 mm

ED8000RT-XFR
ED10000RT-XFR

ED5000RT-XFR
ED6000RT-XFR

25.9 x 17.3 x 5.14"
659 x 440 x 130.6 mm

30.7 x 23.6 x 10.9"
780 x 600 x 276 mm

NOTE:

  Specifications are subject to change without notice.

Connection

Attached 2' open-end
#10 AWG power cord

Terminal Block
Hardwire only

10KVA / 10K Watts

Power (Max)

5KVA / 5K Watts

<50 dBA

Harmonic Distortion

<3% (Full Linear Load)

IF THE STEP DOWN TRANSFORMER  REQUIRES SERVICE

1. Use the Troubleshooting section in the UPS user's manual to eliminate ob-

vious causes.

2. Verify there are no tripped circuit breakers.  A tripped circuit breaker is

the most common issue.

3. Call your dealer for assistance.  If you cannot reach your dealer, or if they

cannot resolve the issue call or fax the Technical Support department at
the following numbers; Voice phone (972) 446-7363, FAX line (972) 446-
9011 or visit our Web site at www.minutemanups.com the "Discussion
Board".  Before calling the Technical Support Department have the follow-
ing information available:
a)

Contact name and address.

b)

Where and when the unit was purchased.

c)

All of the model information about your unit.

d)

The serial number of your unit.

e)

Any information on the failure, including LEDs that may be illuminat-
ed or error codes displayed.

f)

A description of the protected equipment including model numbers, if
possible.

g)

A technician will ask you for the above information and if possible,
help solve the issue over the phone.  In the event that the unit requires
factory service, the technician will issue you a Return Material Autho-
rization Number (RMA #).

h)

If the unit is under warranty, the repairs will be done at no charge.  If
the unit is not under warranty there will be a charge for the repair.

4. Pack the unit in its original packaging.  If the original packaging is no lon-

ger available, ask the Technical Support Technician about obtaining a new
set.  It is important to pack the unit properly in order to avoid damage in
transit.  Never use Styrofoam beads for a packing material.
a)

Include a letter with your name, address, day time phone number,
RMA number, a copy of your original sales receipt, and a brief desc-
ription of the problem.

5. Mark the RMA # on the outside of all packages.  The factory cannot accept

any package without the RMA # marked on the outside.

6. Return the unit by insured, prepaid carrier to:

Para Systems Inc.

MINUTEMAN UPS

1809 W. Frankford Road, Suite 150

Carrollton, TX 75007

ATTN: RMA # _______

Chapter 5: Obtaining Service

Содержание ED10000R T-XFR

Страница 1: ... s Manual Endeavor 5 10KVA Step Down Transformer Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000473 R2 ...

Страница 2: ...1 1 Introduction 2 2 Rear Panels 6 3 Installation 8 4 Operation 14 5 Obtaining Service 16 6 Specifications 17 7 Limited Product Warranty 18 A1 Declaration of Conformity 19 Table Of Contents ...

Страница 3: ... equipment the user must ensure that the ED XFR is properly grounded due to a possible risk of AC current leakage CAUTION This ED XFR series is ONLY intended to be installed in an indoor temperature controlled environment that is free of conductive contaminants This ED XFR series is not intended for use in a computer room as defined in the Standard for the Protection of Electronic Computer Data Pr...

Страница 4: ...e reasonable protection against such interference in a residential installation This equip ment generates and uses radio frequency and if not installed and used properly that is in strict accordance with the manufacturer s instructions this equip ment may cause interference to radio and television reception If this equip ment does cause interference to radio or television reception which can be de...

Страница 5: ...rheated 12 Input voltage selection switch 208 240V The default setting is 208V 1 The Load 4 circuit breaker will trip in the event the load exceeds the power rating 2 Load 4 120V output receptacles 4 5 15 20R 3 The Load 2 circuit breaker will trip in the event the load exceeds the power rating 4 Load 2 120V output receptacles 4 5 15 20R 5 The Load 2 circuit breaker will trip in the event the load ...

Страница 6: ...nt Configuration to install the unit into the rack USE CAUTION The ED XFR UPS and Battery Pack are extremely heavy Use the appropriate number of personnel when installing the UPS system CAUTION DO NOT USE THE MOUNTING BRACKETS TO LIFT THE STEP DOWN TRANSFORMER The mounting brackets are ONLY for securing the unit to the rack Chapter 3 Installation RACKMOUNT CONFIGURATION Use the included rackmount ...

Страница 7: ...ing of these ED XFR 1 Before connecting to the input output terminals read all of the Cautions and Warning then observe the following a Ensure that the UPS is turned off and not connected to the AC sour ce or the battery source before any connections are made b Calculate the power consumption of the load to ensure that an over load condition does not occur c Ensure that the terminal block screws a...

Страница 8: ...rear panel of the ED XFR to the appropr iate voltage 208V 240V NOTE The default setting is 208V The ED XFR s input voltage setting must be the same as the UPS s output voltage set ting 6 Plug the equipment into the output receptacles on the rear panel of the ED XFR NOTE Default voltages for the output receptacles are 120V and 208V Load 2 ouput receptacle can be changed to supply 240V but this chan...

Страница 9: ...nd release the On Off Test Button after the first beep to turn the UPS on 5 The UPS will start up and perform a self diagnosis for approximately 10 seconds The UPS system is ready for normal opeartion See the UPS user s manual for more information 120V outputs La N 50A max Lb N 50A max the combined total for both 83 4A max 208V output Lc Ld 48 1A max 240V output La Lb 41 7A max NOTE Default voltag...

Страница 10: ... tripped circuit breakers A tripped circuit breaker is the most common issue 3 Call your dealer for assistance If you cannot reach your dealer or if they cannot resolve the issue call or fax the Technical Support department at the following numbers Voice phone 972 446 7363 FAX line 972 446 9011 or visit our Web site at www minutemanups com the Discussion Board Before calling the Technical Support ...

Страница 11: ...the equipment is damaged by the customer is improp erly used is subjected to an adverse operating environment or is operated outside the limits of its electrical specifications b the equipment is repaired or modified by anyone other than Para Systems or Para Systems approved personnel or c has been used in a manner contrary to the product s User s Manual or other written instructions Any technical...

Страница 12: ...21 20 Notes Notes ...

Отзывы: