INPUT / OUTPUT CONNECTIONS:
WARNING:  Qualified Service Personnel ONLY 

must perform the Installa-

tion and Servicing of these ED-XFR.
1.

Remove the terminal block cover box from the rear panel of the UPS (re-
quires a phillips screwdriver).  Refer to the figure below for the input / out-
put connections for the UPS.  See the UPS user's manual for connecting
the UPS's input and output cables.

2. Input / Output cable selection:

60°C / 75°C

Temperature Rating

5/6KVA

#10 AWG (Cu)

8/10KVA

#6 AWG (Cu)

(In accordance with National Electrical Code (NEC), install suitable con-
duit and bushing.) 

 

NOTE:

  Use copper wire only.

3. Before connecting to the input / output terminals read all of the Cautions and

Warning.  The AC inputs of these Step Down Transformers are 

ONLY

 intend-

ed to be connected to the output of their respective UPS models.  

NOTE:

The ED-XFR's input voltage setting must be the same as the UPS's output
voltage setting.

ED5000RT-XFR and ED6000RT-XFR:

See the UPS users manual for UPS input and output connections.  Connect the
attached #10 AWG input power cord on the ED-XFR to the output terminal block on
the UPS.
1.  Connect the black wire labeled L on the attached input power cord to the UPS

output terminal block labeled L and secure.

2.  Connect the white wire labeled N on the attached input power cord to the UPS

output terminal block labeled N and secure.

3.  Connect the green wire labeled G on the attached input power cord to the UPS

output terminal block ground terminal and secure.

4. Before re-installing the terminal block cover box on the UPS, see the UPS us-

ers manual for the UPS input and output connections.

5. Set the input voltage select switch on the rear panel of the ED-XFR to the appropr-

iate voltage (208V / 240V).  

NOTE:  

The default setting is 208V.  The ED-

XFR's input voltage setting must be the same as the UPS's output voltage set-
ting.

6. Plug the equipment into the output receptacles on the rear panel of the ED-

XFR.

NOTE:  

Default voltages for the output receptacles are 120V and 208V.  Load 2

ouput receptacle can be changed to supply 240V, but this change must be done at
the factory.

ED8000RT-XFR and ED10000RT-XFR:

1. Remove the terminal block cover plate from the rear panel of the ED-XFR

(requires a phillips screwdriver).  Refer to the figure below for the input / output
connections for the ED8000RT-XFR / ED10000RT-XFR.  Connect the end of
the #6 AWG input power cable labeled "TO XFR" to the appropriate terminals
on the AC input terminal block on the ED-XFR and secure.  The pins for thein-
put cable are included.
a)

Connect the black wire labeled L1 / L2 on the input power cable to the ED-
XFR AC input terminal block labeled L1 for 240V or L2 for 208V and se-
cure.  

NOTE: 

 The ED-XFR's input voltage setting must be the same as

the UPS's output voltage setting.

b)

Connect the white wire labeled L3 on the input power cable to the ED-
XFR AC input terminal block labeled L3 and secure.

The ED8000RT-XFR and ED10000RT-XFR come with an #6 AWG input power
cable in the box.  The pins for the input cable are included.  Connect one end
of the input power cable to the input terminal block on the ED-XFR.  Connect
the other end of the input power cable to the output terminal block on the UPS.
The AC inputs of these Step Down Transformers are 

ONLY 

intended to be

connected to the output of their respective UPS models.  Do not use extension
cords, adapter plugs, or surge strips.  The installation of upstream and down-
stream protective devices is highly recommended when the UPS system is
connected to the mains and the load.

Содержание ED10000R T-XFR

Страница 1: ... s Manual Endeavor 5 10KVA Step Down Transformer Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000473 R2 ...

Страница 2: ...1 1 Introduction 2 2 Rear Panels 6 3 Installation 8 4 Operation 14 5 Obtaining Service 16 6 Specifications 17 7 Limited Product Warranty 18 A1 Declaration of Conformity 19 Table Of Contents ...

Страница 3: ... equipment the user must ensure that the ED XFR is properly grounded due to a possible risk of AC current leakage CAUTION This ED XFR series is ONLY intended to be installed in an indoor temperature controlled environment that is free of conductive contaminants This ED XFR series is not intended for use in a computer room as defined in the Standard for the Protection of Electronic Computer Data Pr...

Страница 4: ...e reasonable protection against such interference in a residential installation This equip ment generates and uses radio frequency and if not installed and used properly that is in strict accordance with the manufacturer s instructions this equip ment may cause interference to radio and television reception If this equip ment does cause interference to radio or television reception which can be de...

Страница 5: ...rheated 12 Input voltage selection switch 208 240V The default setting is 208V 1 The Load 4 circuit breaker will trip in the event the load exceeds the power rating 2 Load 4 120V output receptacles 4 5 15 20R 3 The Load 2 circuit breaker will trip in the event the load exceeds the power rating 4 Load 2 120V output receptacles 4 5 15 20R 5 The Load 2 circuit breaker will trip in the event the load ...

Страница 6: ...nt Configuration to install the unit into the rack USE CAUTION The ED XFR UPS and Battery Pack are extremely heavy Use the appropriate number of personnel when installing the UPS system CAUTION DO NOT USE THE MOUNTING BRACKETS TO LIFT THE STEP DOWN TRANSFORMER The mounting brackets are ONLY for securing the unit to the rack Chapter 3 Installation RACKMOUNT CONFIGURATION Use the included rackmount ...

Страница 7: ...ing of these ED XFR 1 Before connecting to the input output terminals read all of the Cautions and Warning then observe the following a Ensure that the UPS is turned off and not connected to the AC sour ce or the battery source before any connections are made b Calculate the power consumption of the load to ensure that an over load condition does not occur c Ensure that the terminal block screws a...

Страница 8: ...rear panel of the ED XFR to the appropr iate voltage 208V 240V NOTE The default setting is 208V The ED XFR s input voltage setting must be the same as the UPS s output voltage set ting 6 Plug the equipment into the output receptacles on the rear panel of the ED XFR NOTE Default voltages for the output receptacles are 120V and 208V Load 2 ouput receptacle can be changed to supply 240V but this chan...

Страница 9: ...nd release the On Off Test Button after the first beep to turn the UPS on 5 The UPS will start up and perform a self diagnosis for approximately 10 seconds The UPS system is ready for normal opeartion See the UPS user s manual for more information 120V outputs La N 50A max Lb N 50A max the combined total for both 83 4A max 208V output Lc Ld 48 1A max 240V output La Lb 41 7A max NOTE Default voltag...

Страница 10: ... tripped circuit breakers A tripped circuit breaker is the most common issue 3 Call your dealer for assistance If you cannot reach your dealer or if they cannot resolve the issue call or fax the Technical Support department at the following numbers Voice phone 972 446 7363 FAX line 972 446 9011 or visit our Web site at www minutemanups com the Discussion Board Before calling the Technical Support ...

Страница 11: ...the equipment is damaged by the customer is improp erly used is subjected to an adverse operating environment or is operated outside the limits of its electrical specifications b the equipment is repaired or modified by anyone other than Para Systems or Para Systems approved personnel or c has been used in a manner contrary to the product s User s Manual or other written instructions Any technical...

Страница 12: ...21 20 Notes Notes ...

Отзывы: