© MINOTAIR Ventilation Inc. - www.minotair.com
(PENTACARE-V12-OWNER'S MANUAL-2019-Rev-014)
•
The main
ducts’ diameter depend
s on the airflow that was calculated at the
previous step. If the calculated airflow is 90 cfm (40 l/s) or less, it is possible to use
main ducts of 6
”
(150 mm). The maximum airflow of the main ducts will then be
required to be adjusted between 180 cfm and 215 cfm (85 l/s and 100 l/s) in the
microcontroller’s ventilation menu
. Note, however, that this setting will decrease
heating and cooling capacity in heat pump mode by up to approximately 25%
depending on current temperatures and humidity level.
•
If enough space is available, it is always preferable to choose main ducts of
8
”
(200 mm) to use the MINOTAIR to its full. The maximum airflow of the main
ducts will then be required to be adjusted between 220 cfm and 250 cfm (105 l/s
and 120 l/s)
in the microcontroller’s ventilation menu
. If space does not allow the
use of 8
”
(200 mm) ducts for all main ducts, you must favor the main distribution
duct (fresh air to building) to minimize the ventilation noise at the supply grilles.
•
IMPORTANT!
In high speed or heat pump mode, airflow increases significantly. To
minimize the noise of the air in motion, it is recommended to have a minimum
number of supply and return ducts based on whether the main ducts are 6
”
(150 mm)
or 8
”
(200 mm) in diameter:
o
Main ducts
–
6
”
(150 mm) for an airflow ranging between
180 cfm and 215 cfm (85 l/s and 100 l/s):
Minimum recommendations for
supply
ducts:
▪
Minimum 2 x 6" (150 mm) duct, or
▪
Minimum 1 x 6" (150 mm) duct and 2 x
5”
(125 mm), or
▪
Minimum 4 x
5”
(125 mm) ducts.
Minimum recommendations for
return
ducts:
▪
Minimum 1 x 6" (150 mm) duct and 1 x
5”
(125 mm), or
▪
Minimum 3 x
5”
(125 mm) ducts.
o
Main ducts
–
8" (200 mm) for an airflow ranging between
220 cfm and 250 cfm (105 l/s and 120 l/s):
Minimum recommendations for
supply
ducts:
▪
Minimum 3 x 6" (150 mm) ducts, or
▪
Minimum 2 x 6" (150 mm) duct and 2 x
5”
(125 mm), or
▪
Minimum 1 x 6" (150 mm) duct and 3 x 5" (125 mm, or
▪
Minimum 5 x 5" (125 mm) ducts.
Minimum recommendations for
return
ducts:
▪
Minimum 2 x 6" (150 mm) ducts, or
▪
Minimum 1 x 6" (150 mm) duct and 2 x 5" (125 mm), or
▪
Minimum 4 x 5" (125 mm) ducts.