15
5-2-2.
Relay zone
1)
Remote input (Master
→
Instrument)
4 stations occupied
Device No.
Contents Classification
RYn0
①
Setting value writing request (Request 1)
Communication
RYn1
RYn2
②
General command request (Request 2)
RYn3
③
Selection of writing/Reading out. (R/W)
RYn4
④
Operation mode changeover request (Request 3)
RYn5
RYn6
RYn7
RYn8
RYn9
RYnA
RYnB
RYnC
RYnD
RYnE
RYnF
RY(n+1)0
⑤
Zero
Control signal
RY(n+1)1
⑥
Zero clear
RY(n+1)2
⑦
Tare
RY(n+1)3
⑧
Tare clear
RY(n+1)4
⑨
Hold
RY(n+1)5
⑩
Net display
RY(n+1)6
⑪
Gross display
RY(n+1)7
RY(n+1)8
⑫
Accumulation signal
RY(n+1)9
⑬
Accumulation clear
RY(n+1)A
⑭
Error cancellation request flag
RY(n+1)B
RY(n+1)C
RY(n+1)D
RY(n+1)E
RY(n+1)F
RY(n+2)0
⑮
Brand number
10
0
1
RY(n+2)1 2
RY(n+2)2 4
RY(n+2)3 8
RY(n+2)4
10
1
10
RY(n+2)5 20
RY(n+6)6 40
RY(n+6)7 80
~
RY(n+7)0
System reservation zone
RY(n+7)1
RY(n+7)2
RY(n+7)3
RY(n+7)4
RY(n+7)5
RY(n+7)6
RY(n+7)7
RY(n+7)8
RY(n+7)9
⑯
Initialed data setting request flag
RY(n+7)A
⑰
Error reset requesting flag
RY(n+7)B
RY(n+7)C
RY(n+7)D
RY(n+7)E
RY(n+7)F
n : Value decided by setting of station No.