MP 26/10
Installation and Calibration Manual
Minebea Intec
EN-29
Configure the output
3.
Go to the required Out.x and set the parameters below.
Name
Value
Description
O.Act
Direction of operation OUT1
0
Direct / normally open
1
Inverse / normally closed
Lim.1
Signal limit 1(Result of comparison of limit 1 values
with actual weight
0
not active
1
active
Lim.2
Signal limit 2 (Result of comparison of limit 2 values
with actual weight)
0
not active
1
active
Lim.3
Signal limit 3 (Result of comparison of limit 3
values with actual weight)
0
not active
1
active
FAi.1
Signal INP fail
0
not active
1
active
Set the values for limit processing
4.
Go to Parameter
Limit.
5.
Set the limit values based on the output requirement.
limits
Range
Description
L.1
-1999...9999
Display value Lower Limit (L.1< -1999 then L.1 is off )
H.1
-1999...9999
Display value Upper Limit (L.1< -1999 then H.1 is off )
HYS.1
0...9999
Hysteresis for limit value 1
L.2
-1999...9999
Display value Lower Limit (L.2< -1999 then L.1 is off )
H.2
-1999...9999
Display value Upper Limit (L.2< -1999 then H.1 is off )
HYS.2
0...9999
Hysteresis for limit value 2
L.3
-1999...9999
Display value Lower Limit (L.3< -1999 then L.1 is off )
H.3
-1999...9999
Display value Upper Limit (L.3< -1999 then H.1 is off )
HYS.3
0...9999
Hysteresis for limit value 3
The limit value processing is shown below.