Minco TT190 Скачать руководство пользователя страница 3

3

Installation

 of TT190 and TT230 Temptrans

TM

 in Class I, Divisions 1 or 2, Groups A, B, C, and D

hazardous locations.

Read these instructions thoroughly before installing transmitters.

Per Factory Mutual,
  1) Installation shall be in accord with these instructions and the National Electric Code.
  2) If installing in a Class I, Division 1 hazardous area, then refer to dwg. INST. 704, "CONTROL

DOCUMENT, SYSTEM APPROVALS FOR INTRINSICALLY SAFE TRANSMITTERS" on pages
5-7 of this manual.

  3) If installing in a Class I, Division 2 hazardous area, the transmitters must be mounted in a vent-

free enclosure, meeting the "Electrical Utilization Enclosure Requirements" stated below with
which only the Approved equipment will be installed.  All unused openings should be sealed.

  4) Tampering and replacement with non-factory components may adversely affect the safe use of

the system.

Electrical Utilization Enclosure Requirements (Required for Division 2 areas only)

1.  Each of the transmitters must be mounted within an enclosure to prevent personal injury resulting
from accessibility to live parts.  This enclosure must comply with the requirements listed below.
Further details of the enclosure requirements may be found in ANSI/ISA Standards S82.01, S82.02,
and S82.03.

1.1  Accessibility - The transmitters must be installed within the enclosure so that its circuits are
accessible by the use of a tool only.  A part is accessible when a) the IEC articulate accessibility
probe applied in every possible position to the exterior or exposed surfaces, including the bottom,
or b) the IEC rigid accessibility probe applied with a maximum force of 30 newtons (6.75 lbs
force) in every possible position to the exterior or exposed surface, including the bottom, touches
the part.

1.2  Protection From Fire - If the enclosure is non-metallic, it shall have the proper flammability
rating as detailed within ANSI/ISA Standard S82.01.

1.3  Grounding - A metallic enclosure must have a protective grounding terminal and be marked
as such.  The size of the ground terminal is to be equivalent to the size of the supply circuit
conductor terminals.  All accessible non-current conductive parts must be bonded to the
protective grounding terminal.

1.4  General Construction - The equipment enclosure, or parts of the enclosure, required to be in
place to comply with the requirements for protection from electric shock, personal injury,
protection from internal parts and wiring, and external cord and cable assembly strain relief shall
comply with the following tests for mechanical strength:

Содержание TT190

Страница 1: ...emperature Transmitters Installation and Operating Instructions INTRINSICALLY SAFE NON INCENDIVE MINCO MINCO PRODUCTS INC 7300 Commerce Lane Minneapolis Minnesota 55432 3177 U S A Telephone 763 571 31...

Страница 2: ...re to installation requirements as set forth by the National Electrical Code NEC and any other applicable codes and standards See pages 3 7 for further information on installing these transmitters in...

Страница 3: ...ure requirements may be found in ANSI ISA Standards S82 01 S82 02 and S82 03 1 1 Accessibility The transmitters must be installed within the enclosure so that its circuits are accessible by the use of...

Страница 4: ...nch in diameter the end of which is rounded The force shall be applied for one minute to any point on the overall enclosure except the bottom The bottom shall sustain a force of 65 Newtons 15 pounds c...

Страница 5: ...5...

Страница 6: ...6...

Страница 7: ...7...

Страница 8: ...hen the span 200 50 250 C Temperature Span T C Type K E J K T K Connect RB range RC range RE range 1 A 50 to 70 C 150 to 200 C 300 to 400 C 2 A 70 to 100 C 200 to 300 C 400 to 600 C 3 A 100 to 200 C 3...

Страница 9: ...epeated However it is recommended that step 5 be repeated to check that meter still reads 4 mA to ensure proper calibration Warranty Items returned within one year from the date of sale transportation...

Страница 10: ...ula Rloop max Vsupply 10 02 amps Maximum Output Current 27 mA Connections Terminal blocks for wires from AWG 22 to AWG 14 Physical Epoxy potted for moisture resistance Weight 1 8 oz 58 grams Model Num...

Отзывы: