TT190 and TT230

2-wire Temperature Transmitters

Installation and Operating Instructions

            

INTRINSICALLY  SAFE

                        

NON-INCENDIVE

MINCO

MINCO

 PRODUCTS, INC.

7300 Commerce Lane, Minneapolis, Minnesota 55432-3177 U.S.A.
Telephone: (763)571-3121                      FAX: (763)571-0927

TT190

TT230

Содержание TT190

Страница 1: ...emperature Transmitters Installation and Operating Instructions INTRINSICALLY SAFE NON INCENDIVE MINCO MINCO PRODUCTS INC 7300 Commerce Lane Minneapolis Minnesota 55432 3177 U S A Telephone 763 571 31...

Страница 2: ...re to installation requirements as set forth by the National Electrical Code NEC and any other applicable codes and standards See pages 3 7 for further information on installing these transmitters in...

Страница 3: ...ure requirements may be found in ANSI ISA Standards S82 01 S82 02 and S82 03 1 1 Accessibility The transmitters must be installed within the enclosure so that its circuits are accessible by the use of...

Страница 4: ...nch in diameter the end of which is rounded The force shall be applied for one minute to any point on the overall enclosure except the bottom The bottom shall sustain a force of 65 Newtons 15 pounds c...

Страница 5: ...5...

Страница 6: ...6...

Страница 7: ...7...

Страница 8: ...hen the span 200 50 250 C Temperature Span T C Type K E J K T K Connect RB range RC range RE range 1 A 50 to 70 C 150 to 200 C 300 to 400 C 2 A 70 to 100 C 200 to 300 C 400 to 600 C 3 A 100 to 200 C 3...

Страница 9: ...epeated However it is recommended that step 5 be repeated to check that meter still reads 4 mA to ensure proper calibration Warranty Items returned within one year from the date of sale transportation...

Страница 10: ...ula Rloop max Vsupply 10 02 amps Maximum Output Current 27 mA Connections Terminal blocks for wires from AWG 22 to AWG 14 Physical Epoxy potted for moisture resistance Weight 1 8 oz 58 grams Model Num...