MENU  SELECTIONS

PRIMARY MENU
Press INDEX to advance to the next menu item.  Press UP ARROW or DOWN ARROW
to change the value in the display.  Press ENTER to retain the value.

SP

Set Point Adjust, Control Point.

SECONDARY MENU
Press UP ARROW ENTER simultaneously.  Press INDEX to advance to the next menu
item.  Press UP ARROW or DOWN ARROW to change the value in the display.    Press
ENTER to retain the value.

ALLo Alarm Low: The Low Alarm point is usually set below the Set Point.

ALHi Alarm High: The High Alarm Point is usually set above the Set Point.

CY

Cycle Rate and output selection: Select OnOF, 1, 2 to 80 seconds total cycle time.
ONOF A setting of ONOF allows the control to operate as a simple on/off mode.

This setting forces the control to turn off at set point, and on at the set point
plus the differential (SP_d). When selected, the tunE, Pb, rES, OFS, rtE,
and ArUP 
selections in the Secondary menu and the SPOL and SPOH
selections in the Secure menu are suppressed.

1

A setting of 1 is recommended for solid state outputs (SSR or 5VDC).

2 to 80 Time Proportioning Control is adjustable in 1 sec. steps. Recommended for

mechanical outputs (relays, solenoids, etc.).  For best contact life, a time
should be selected that is as long as possible without causing the process
to wander.

SP_d Set Point On-Off Differential.  (Only appears if CY is set to ONOF.) Select to 999°F.

This value will be negative for reverse acting set points, and positive for direct acting
outputs.  Set the value for the amount of temperature difference between the turn
off point (set point) and the turn on point.

tunE Tuning Choice: Select SELF or Pid.

SELF The Controller will evaluate the Process and select the PID values to

maintain good control.  The ramp function (rt) cannot be selected while
SELF tunE is active.  The temperature descriptor will flash while SELF tunE
is active.  The control will switch to Pid tunE when the tuning function is
complete.

Pid

Manually adjust the PID values. PID control consists of three basic
parameters, Proportional Band (Gain), Reset Time (Integral), and Rate
Time (Derivative).

Pb

Proportional Band (Bandwidth): Select 5 to 5000 °F (3 to 2778 °C).

rES

Automatic Reset Time: Select OFF0.1 to 99.9 minutes. Select OFF
to switch to OFS.

OFS   Manual Offset Correction: Select OFF, 0.1 to 99.9%. Select OFF to

switch to rES.

rtE

Rate Time. Select OFF, 0.01 to 99.99 minutes (Derivative).

Page 7 of 12

ArUP Anti- Reset Wind-up Feature: Select On or OFF.

On

If ArUP is On the accumulated Reset Offset value will be cleared to 0%
when the process input is not within the Proportional Band.

OFF

If ArUP is OFF, the accumulated Reset Offset Value is retained in memory
when the process input is not within the Proportional Band.

rt

Ramp Time:  Select OFF00.01 to 99.59 (HH.MM).  When value is entered, control
calculates a ramp slope from the current temperature to SP over the time entered.
Changing rt or SP (or pressing ENTER at either menu item) restarts the ramp
function, and re-calculates the slope.  The right hand decimal point of the display
will flash while the ramp function is active.  Self tunE cannot be selected while the
ramp function is active.  Selecting OFF will stop a current ramp and drive the output
as necessary to reach set point

InPC Input Correction: Select ±500 °F (±278 °C). This feature allows the input value to

be changed to agree with an external reference or to compensate for sensor error.
Note:  InPC is reset to zero when the input type is changed, or when decimal
position is changed.

FiLt

Digital Filter: Select OFF, 1 to 99. In some cases the time constant of the sensor,
or noise could  cause the display to jump enough to be unreadable. A setting of 2
is usually sufficient to provide enough filtering for most cases, (2 represents
approximately a 1 second time constant). When the 0.1 degree resolution is
selected this should be increased to 4.  If this value is set too high, controllability
will suffer.

SECURE MENU
Hold UP ARROW ENTER for 5 Seconds.  Press INDEX to advance to the next menu item.
Press UP ARROW or DOWN ARROW to change the value in the display.    Press ENTER
to retain the value.

SECr Security Code: See the Security Level Selection and the Password Table in this

manual in order to enter the correct password.

InP

Input Type: Select one of the following. The selections are limited to the input type
you ordered.  If you ordered a thermocouple input control, make your selection from
the thermocouple list.  If you ordered an RTD input, select from the RTD list.

Thermocouple selections:

J-IC Type “J” Thermocouple, Iron/Constantan (NIST)
CA

Type “K” Thermocouple Chromel/Alumel

t-

Type “T” Thermocouple Copper/Constantan

RTD selection:

P385 100 ohm Platinum (DIN 0.00385 

Ω/Ω

/°C), element code PD.

F-C

Select temperature descriptor for Fahrenheit or Celsius.
F

°F descriptor is On and temperature inputs will be displayed in actual
degrees Fahrenheit.

C

°C descriptor is On and temperature inputs will be displayed in actual
degrees Celsius.

dPt

Decimal Point Positioning: Select 0 or 0.0.  This only affects the Process Value, SP,
ALLo, ALHi, and InPC.
0

No decimal Point is selected.

0.0

One decimal place is selected.  If the Process Value moves outside of the
decimal point range ends (-199.9 to +999.9), the Process Value display will
autorange to whole degree resolution.  When the Process Value returns to
the decimal point range, the display will autorange back to tenth degree
resolution.

Содержание CT15 Series

Страница 1: ...TIONS FOR THE CT15 SERIES MICROPROCESSOR BASED TEMPERATURE CONTROLLER MODEL IDENTIFICATION Alarm 0 No 1 Yes Input 1 Thermocouple J K T 2 100 Platinum RTD DIN element PD Model CT15 Output 1 SSR 2 5 VDC...

Страница 2: ...he factory programmed for type J thermocouples Suppose for this example you wish to change the input to type K and limit the set point range between 0 and 1000 C First entertheSECUREMENUasinstructedon...

Страница 3: ...the front of the panel slide the housing through the cut out The housing gasket should be against the housing flange before installing From the rear of the panel slide themountingcollaroverthehous ing...

Страница 4: ...ons are as follows 1 INDEX Pressing the INDEX key advances the display to the next menu item May also be used in conjunction with other keys as noted below 2 UP ARROW Increments a value changes a menu...

Страница 5: ...MARY MENU quickly from any other menu press the UP ARROW ENTER keys followed by pressing the INDEX DOWN ARROW keys SECURITY LEVEL SELECTION NOTE Lock menus to prevent unauthorized changes to controlle...

Страница 6: ...tioning Control is adjustable in 1 sec steps Recommended for mechanical outputs relays solenoids etc For best contact life a time should be selected that is as long as possible without causing the pro...

Страница 7: ...constant When the 0 1 degree resolution is selected this should be increased to 4 If this value is set too high controllability will suffer SECURE MENU Hold UPARROW ENTERfor5Seconds PressINDEXtoadvan...

Страница 8: ...FF Lamp OFF when Output is ON ALARM TYPE AND ACTION if present Caution In any critical application where failure could cause expensive product loss or endanger personal safety a redundant limit contro...

Страница 9: ...anged the Alarm Point will track with SP ALrE Alarm Reset Select OnOF or Hold OnOF Automatic Reset Hold ManualReset Acknowledge reset bysimultaneouslypressingtheINDEX DOWN ARROW keys for 5 sec ALPi Al...

Страница 10: ...OFL bAd InP OPEn InP CHEC CAL No dis play lighted FAIL tESt CHEC SP CHEC ALLO CHEC ALHi CHEC SPL or CHEC SPH MEANING Underflow or Overflow Process value has ex ceeded input range ends UFLorOFLwillseq...

Страница 11: ...bility 0 05 over the supply voltage range Temperature Stability 4 V C 2 3 V F typical 8 V C 4 5 V F maximum Common Mode Rejection 140 db minimum at 60 Hz Normal Mode Rejection 65 db typical 60 db at 6...

Страница 12: ...th Seller s instructions and the defect is not caused by shipping damage misuse or abuse by the Buyer There are no other warranties written oral or implied The liability of the Seller is limited to th...

Отзывы: