Page EN-16
Pointek ULS200 – QUICK START MANUAL
7ML19981XB83
mmmmm
English
Fail-Safe Mode
In the event that a loss of echo condition exceeds the fail-safe timer (speed of response
variable), ? appears in the display; and if a relay is assigned to LOE (alarm function
option), it is engaged. This function must be used with the Output Function on page 13.
* Factory setting
Fail-Safe Timer
The fail-safe timer allows the user to vary the waiting period from the time of a loss of
echo or operating fault condition begins, until the fail-safe default is effected. The waiting
period is adjustable from 1 to 15 minutes, in 1 minute increments.
Units
The units of the measurement reading can be selected as follows:
1 = metres, m
(Factory setting)
2 = feet, ft
The selected units are also applicable to the Blanking and Relay adjustments.
Troubleshooting
The echo is not reliable and Pointek ULS200 is waiting for a valid echo
before updating the measurement.
Maintenance
Pointek ULS200 requires no maintenance or cleaning.
Unit Repair and Excluded Liability
For detailed information, please see the inside back cover.
fail-safe
mode
function
reading
high and high-high
low and low-low
1
high
on
off
hold
2
low
off
on
hold
3*
hold
hold
hold
hold
Probable causes are:
Remedy
material or object in contact with sensor face
lower material level or raise Pointek ULS200
Pointek ULS200 is not perpendicular to the material
surface
check Pointek ULS200 mounting
if angle of repose is too steep, angle Pointek
ULS200 mounting
change in level too fast
adjust speed of response
material out of range
acceptable on some high level switch applications
foam on liquid surface
mount Pointek ULS200 via stilling well or pipe
too much dust or interference from material filling
relocate Pointek ULS200
high level of vibration in the mounting structure
relocate Pointek ULS200 or limit vibration
material inside blanking zone or below range limit
adjust blanking or range limit
Fail-safe default after prolonged Loss Of Echo.
Investigate the probable causes listed above.
Содержание pointek uls200
Страница 1: ...Quick Start Manual March 2010 ULS200 pointek...
Страница 2: ...IQ300IX fm Page 5 Tuesday October 2 2001 1 43 PM...
Страница 20: ...Page EN 18 Pointek ULS200 QUICK START MANUAL 7ML19981XB83 mmmmm English...
Страница 38: ...Side DA 18 Pointek ULS200 KVIKSTART MANUAL 7ML19981XB83 mmmmm Dansk...
Страница 56: ...Seite DE 18 Pointek ULS200 KURZANLEITUNG 7ML19981XB83 mmmmm Deutsch...
Страница 63: ...7ML19981XB83 Pointek ULS200 EL 7 mmmmm AC DC DC DC IEC 61010 1 250 V DC AC DC 18 30 V 100 230 V AC 18 30 V DC...
Страница 74: ...EL 18 Pointek ULS200 7ML19981XB83 mmmmm...
Страница 92: ...P gina ES 18 Pointek ULS200 GU A PARA LA PUESTA EN MARCHA R PIDA 7ML19981XB83 mmmmm Espa ol...
Страница 110: ...Page FR 18 Pointek ULS200 MISE EN SERVICE SIMPLIFIEE 7ML19981XB83 mmmmm Fran ais...
Страница 128: ...Pagina IT 18 Pointek ULS200 MANUALE PER L AVVIO RAPIDO 7ML19981XB83 mmmmm Italiano...
Страница 146: ...Pagina NL 18 Pointek ULS200 QUICK START HANDLEIDING 7ML19981XB83 mmmmm Nederlands...
Страница 164: ...P gina PT 18 Pointek ULS200 MANUAL DE ARRANQUE R PIDO 7ML19981XB83 mmmmm Portugu s...
Страница 182: ...Sivu SU 18 Pointek ULS200 PIKAK YTT OPAS 7ML19981XB83 mmmmm Suomi...
Страница 200: ...Sida SV 18 Pointek ULS200 MANUAL F R SNABBSTART 7ML19981XB83 mmmmm Svenska...