OM-2223 Page 19
B. 900 Ampere Rated Welding Output
50 Hz
Input Voltage
380
400
440
Input Amperes At Rated Output
101
96
87
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay
2
125
110
100
Normal Operating
3
150
150
125
Min Input Conductor Size In AWG
4
2
3
3
Max Recommended Input Conductor Length In Feet (Meters)
353
(108)
325
(99)
393
(120)
Min Grounding Conductor Size In AWG
4
6
6
6
Reference: 1999 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
4-12. Placing Jumper Links
Ref. 802 295
Tools Needed:
3/8 in
230 VOLTS
Ref. S-174 973-A
575 VOLTS
460 VOLTS
2
Do not overtighten
jumper link nuts.
380 VOLTS
400 VOLTS
440 VOLTS
Ref. S-174 975-A
1
Y
Disconnect and lockout/tag-
out input power before
installing or moving jumper
links.
Check input voltage available at
site.
1
Jumper Link Label
Check label − only one is on unit.
2
Jumper Link
Move jumper links to match input
voltage, and label on unit.
Close and secure access door, or
go on to Section 4-13.