A complete Parts List is available at www.MillerWelds.com
OM-272989 Page 18
5-3. Electrical Service Guide
Elec Serv 2014
−
01
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
.
Actual input voltage should not exceed
±
10% of indicated required input voltage. If actual input voltage is outside of this range, output may not
be available.
50/60 Hz 240
Single Phase
50/60 Hz 120
Volts AC
Input Voltage (V)
240
A 15 or 20
ampere
individual
branch circuit
protected by
time-delay
fuses or
circuit breaker
is required.
See Section
Input Amperes (A) At Rated Output
29.3
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
35
Normal Operating Fuses
3
40
Min Input Conductor Size In AWG
4
14
Max Recommended Input Conductor Length In Feet (Meters)
51
(16)
Min Grounding Conductor Size In AWG
4
14
Reference: 2014 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
5-4. Extension Cord Data
Input Voltage
Input Power
Phase
Hertz
Conductor Size
Max. Cord Length
120 V
1
50/60
14 AWG
24 ft (7 m)
240 V
1
50/60
14 AWG
51 ft (16 m)
Notes
Work like a Pro!
Pros weld and cut
safely. Read the
safety rules at
the beginning
of this manual.