OM-404 Page 19
5
6
2
3
6-2.
CSA Receptacle Option
If unit does not have GFCI re-
ceptacles, use GFCI-
protected extension cord.
1
120/240 V 50 A AC Recep-
tacle RC1
RC1 supplies 60 Hz single-phase
power at weld/power speed. Maxi-
mum output is 10 kVA/kW.
2
120 V 20 A AC Duplex Recep-
tacle RC2
3
120 V 20 A AC Duplex Recep-
tacle RC3
RC2 and RC3 supply 60 Hz single-
phase power at weld/power speed.
Maximum output from RC2 or RC3
is 2.4 kVA/kW.
4
Circuit Breaker CB1
CB1 protects the ac receptacles
from overload. If CB1 opens, the ac
receptacles do not work.
Move CB1 toggle switch to On
position to reset circuit break-
er. If breaker continues to open,
contact Factory Authorized
Service Agent.
5
Circuit Breaker CB2
6
Circuit Breaker CB3
CB2 protects RC2 and CB3 pro-
tects RC3 from overload. If a circuit
breaker opens, the receptacle does
not work.
Press button to reset circuit
breaker. If breaker continues to
open, contact Factory
Authorized Service Agent.
Combined output of all receptacles
limited to 8.5 kVA/kW rating of the
generator.
EXAMPLE: If 20 A is drawn from
each 120 V duplex receptacle, only
15 A is available at the 240V
receptacle:
2 x (120 V x 20 A) + (240 V x 15 A)
= 8.4 kVA/kW
7
Generator Power While
Welding Label
203 683
4
1
S-166 360-A
See Owner’s Manual for additional information.
Weld Current
In Amperes
Total Power
120V
210
140
90
1000
4300
6000
36
50
8
240V
18
25
4
WITH FINE ADJUST SET AT 10
In Watts
Receptacle
Receptacle
SIMULTANEOUS WELDING AND POWER
7
Amperes
Amperes