A complete Parts List is available at www.MillerWelds.com
OM-278 Page 19
4-15. Connecting Remote Control
Ref. 800 166-D
!
Turn off power before con-
necting a remote control.
1
Remote 14 Receptacle RC8
Connect remote control to RC8.
OR
OR
A
J
B
K
I
C L N
H
D M
G
E
F
1
4-16. Electrical Service Guide
60 Hz Models
50 Hz Models
Input Voltage
230
460
575
380
400
440
520
Input Amperes At Rated Output
126
63
50.4
77
73
66
54
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay
2
150
70
60
90
90
80
60
Normal Operating 3
200
90
80
125
110
100
80
Min Input Conductor Size In AWG
4
1
6
6
4
4
4
6
Max Recommended Input Conductor Length In Feet (Me-
ters)
208
(64)
328
(100)
513
(156)
335
(102)
371
(113)
449
(137)
419
(128)
Min Grounding Conductor Size In AWG
4
6
8
8
6
6
8
8
Reference: 2005 National Electrical Code (NEC)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.