background image

MAS

NTR 735 A

INSTALLATION MANUAL

Simple Automation Control Module (MAS)

ntr_735a_e_mas_installation_manual.doc

07/1999 - 3/8

2.3

Description of inputs

Description

Description of AC inputs

Input voltage

100 - 240V AC, +10% -15%, 50/60 Hz

Input impedance

 800 k Ohms

Level 0

 40V AC

Level 1

 80V AC

Response time

25 ms min, 130 ms max.

Galvanic isolation

No

Status indication

LCD display

Description

Description of DC inputs

Input voltage

24V DC +20% -15%

Current consumption

5 mA

Level 0

 4V

Level 1

 18V

Response time

15 ms

Galvanic isolation

No

Status indication

LCD display

Description

Description of analogue inputs

MAS 10 RCD

6 Inputs: I 01 – I 06

MAS 20 RCD

8 Inputs: I 01 – I 08

Number of bits

8

Resolution

(10000 / 250) mV

Conversion time

15 +/- 5ms

Input voltage

0 - 10V DC

Input impedance

150 k Ohms max.

Precision

+/- 5%

Default Offset/ Gain

Offset = 0
Gain = 1
These values can be changed by the program

Temp. dependent derating

+/- 3 LSB on the authorised range

2.4

Description of relay outputs

Description

Description of relay outputs

Max. operating voltage

250V AC, 30V DC

Max. operating current

8A / point

Minimum load

10mA at 5V DC

Response time

 10ms

Type of contact

Gold-plated silver

Status indication

LCD display

Category

of use

Max. operating

voltage

Power consumption

in steady state

Durability

(number of operations)

Max. ops /

hour

AC15 (electromagnet)

250V AC

450 VA

100000

600

DC13 (electromagnet)
(L/R = 150 ms)

30V DC

10 W

100000

360

AC14 (electromagnet)

250V AC

750 VA

100000

600

AC12 (resistive)

250V AC

2000 VA

100000

1800

DC12 (resistive)

30V DC

192 W

100000

1800

           

Содержание 89 750 001

Страница 1: ...MILLENIUM INSTALLATION MANUAL NTR 735 A E Simple Automation Control Module MAS...

Страница 2: ...l the sensors and actuators in the installation A display on the front panel can be used to check the state of your system at any time The MILLENIUM series is characterised by Ease of programming and...

Страница 3: ...24V DC 24V DC 12 RELAY 8 Available from Q4 1999 2 2 Description of power supplies Description Code Specification Power supply MAS x RCA 100 240V AC 10 15 50 60 Hz MAS x RCD 24V DC 20 15 Micro cuts MA...

Страница 4: ...umber of bits 8 Resolution 10000 250 mV Conversion time 15 5ms Input voltage 0 10V DC Input impedance 150 k Ohms max Precision 5 Default Offset Gain Offset 0 Gain 1 These values can be changed by the...

Страница 5: ...7 Hz 0 15 mm Constant amplitude Acceleration 57 150 Hz 9 8 m s X Y Z 10 times 80 minutes in each direction Resistance to vibrations Mounted on DIN rail JIS C0040 10 57 Hz 0 07 mm Constant amplitude Ac...

Страница 6: ...ater or near any possible leaks Protect the module from external debris during installation Separate the cables and power equipment as far as possible The MILLENIUM series module should be installed i...

Страница 7: ...4 2 Conductor cross section For the inputs outputs use conductors 0 13 mm 3 31 mm 26 12 AWG Strip back the conductor by 7 0 5 mm Undo the terminal screw to its maximum before inserting a conductor To...

Страница 8: ...ON MANUAL Simple Automation Control Module MAS ntr_735a_e_mas_installation_manual doc 07 1999 7 8 4 4 Wiring diagram L N L N NC NC 1 2 3 4 5 6 INPUTS _ A B 1 2 3 4 5 6 INPUTS _ _ A B 1 2 3 4 5 6 INPUT...

Страница 9: ...ed technician This manual uses the symbols below to highlight information relating to the safety of personnel and the protection of equipment Where these symbols appear the associated comments should...

Отзывы: