MAS
NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_installation_manual.doc
07/1999 - 3/8
2.3
Description of inputs
Description
Description of AC inputs
Input voltage
100 - 240V AC, +10% -15%, 50/60 Hz
Input impedance
≥
800 k Ohms
Level 0
≤
40V AC
Level 1
≥
80V AC
Response time
25 ms min, 130 ms max.
Galvanic isolation
No
Status indication
LCD display
Description
Description of DC inputs
Input voltage
24V DC +20% -15%
Current consumption
5 mA
Level 0
≤
4V
Level 1
≥
18V
Response time
15 ms
Galvanic isolation
No
Status indication
LCD display
Description
Description of analogue inputs
MAS 10 RCD
6 Inputs: I 01 – I 06
MAS 20 RCD
8 Inputs: I 01 – I 08
Number of bits
8
Resolution
(10000 / 250) mV
Conversion time
15 +/- 5ms
Input voltage
0 - 10V DC
Input impedance
150 k Ohms max.
Precision
+/- 5%
Default Offset/ Gain
Offset = 0
Gain = 1
These values can be changed by the program
Temp. dependent derating
+/- 3 LSB on the authorised range
2.4
Description of relay outputs
Description
Description of relay outputs
Max. operating voltage
250V AC, 30V DC
Max. operating current
8A / point
Minimum load
10mA at 5V DC
Response time
≤
10ms
Type of contact
Gold-plated silver
Status indication
LCD display
Category
of use
Max. operating
voltage
Power consumption
in steady state
Durability
(number of operations)
Max. ops /
hour
AC15 (electromagnet)
250V AC
450 VA
100000
600
DC13 (electromagnet)
(L/R = 150 ms)
30V DC
10 W
100000
360
AC14 (electromagnet)
250V AC
750 VA
100000
600
AC12 (resistive)
250V AC
2000 VA
100000
1800
DC12 (resistive)
30V DC
192 W
100000
1800