4.

RECORDS

a.

Record the 3 latest tripped faults current or “tSt” for manual trip test.

b.

The records are stored in non-volatile memory.

c.

To clear the entire record database:

Step 1: Press

button until the [FUNC] digit shows “A”. 

 

Step 2:

5.

TECHNICAL DATA

AUXILIARY SUPPLY

DIN310C-230A............................................................... 184~276 VAC
Rated frequency............................................................. 50Hz 
VA rating......................................................................... 3 VA typical

SETTING 

Sensitivity........................................................................ 10mA
Time Delay........................... .......................................... Instantaneous

RECORD

Fault record.................................................................... 3 latest trip fault current or “tSt” for manual trip test
Storage........................................................................... Non-volatile memory

OUTPUT CONTACT

Contact rating................................................................. 5A(NO) / 3A(NC) / 250V AC1
Contact arrangement...................................................... Change over
Expected electrical life.................................................... 10,000 at rated current
Expected mechanical life................................................ 5,000,000 operations

[

] or  [

]

 Press  [

] and [

] buttons simultaneously and hold for 3.5s until

 

the [DATA] shows “0”.

 

INDICATORS

Leakage trip delay time.................................................. Red indicator
Leakage trip.................................................................... 7-segment display and red indicators
Manual test trip............................................................... 7-segment display and red indicators
ZCT connection fault...................................................... 7-segment display and red indicators
Trip records.................................................................... 7-segment display
Real-time leakage current.............................................. 7-segment display

ZERO-PHASE CURRENT TRANSFORMERS

To operate with Mikro's ZCT series of current transformers

MECHANICAL

Mounting......................................................................... Standard 35mm DIN rail mounting
Approximate weight........................................................ 0.4kg (Relay)
Approximate weight........................................................ 0.095kg (ZCT)