Electrical connection U.K.
All electrical work must be carried out
by a suitably qualified and competent
person, in strict accordance with na-
tional and local safety regulations.
Ensure power is not supplied to the ma-
chine while installation work is being
carried out.
The voltage, rated load and fuse rating
are given on the data plate. Please en-
sure these match the site mains supply.
This washer-extractor is supplied as
standard for connection to either:
230 – 240 V / 1 N / 50 Hz,
30 A fuse rating
single phase supply for connection
to a suitable isolator.
or:
400 V /
2 phase + N
/ 50 Hz
2 x 16 A fuse rating
for connection to a suitable isolator.
or:
for off-shore use, WSE 5426
See data plate for fuse rating
for connection to a suitable isolator.
The machine is not convertible.
Connection of single and two
phase machines:
230 – 240 V / 1 N / 50 Hz
(30 A fuse rating U.K.)
400 V /
2 phase + N
/ 50 Hz
(2 x 16 A fuse rating U.K.)
Connection should be made via a suit-
able isolator which complies with na-
tional and local safety regulations, and
the on/off switch should be easily ac-
cessible for servicing work.
For extra safety it is advisable to install
a residual current device (RCD) with a
trip current of 30 mA (in accordance
with DIN VDE 0664, VDE 0100 Section
739).
When switched off there must be an all-
pole contact gap of 3 mm in the isola-
tor switch (including switch, fuses and
relays acc. to VDE 0660).
Important
For
400 V 2 phase
connection, the ma-
chine is supplied with a
4-core
cable in
the following colours:
Black = live
Brown = live
Blue = neutral
Green and yellow = earth.
If a
3 phase
supply is provided on site,
then one of the phases is not used.
WARNING
THIS APPLIANCE MUST
BE EARTHED
Installation
46