Installationsplan / Installation plan: PW 6163 EL/D
Datum / Date: 16.03.2011
Seite / Page: 10
Machine connections:
Electrical
connection
1. Standard voltage (as supplied)
V
3N AC 380-415
Frequency
Hz
50 - 60
Rated load
kW
18.0
Fuse rating
A
3 × 25
Connection cable (to be ordered
separately)
Minimum cross-sectional area
mm²
5 × 4
with threaded cable connector
M 32 x 1.5
Deviations herefrom:
2. Standard voltage (as supplied)
V
3 AC 220-240
Frequency
Hz
50 - 60
Rated load
kW
18.0
Fuse rating
A
3 × 50
Connection cable (to be ordered
separately)
Minimum cross-sectional area
mm²
4 × 10
with threaded cable connector
M 40 x 1.5
Alternative voltage
C
o
n
ver
ti
b
le
V
3 AC 208
Frequency
Hz
60
Rated load
kW
15.3
Fuse rating
A
3 × 50
Connection cable (to be ordered
separately)
Minimum cross-sectional area
mm²
4 × 10
with threaded cable connector
M 40 x 1.5
Connection using multi-pole wall socket in compliance
with IEC 60309 and IEC 60947 is recommended in
order to simplify electrical tests.
Install mains isolator according to IEC 60947 on hard-
wired connection. Wall socket or mains isolator must
be accessible after installation.
The use of an earth leakage circuit breaker (ELCB) is
strongly recommended. A type B RCD (residual
current device) must then be used.
If necessary, equipotential bonding with good
galvanic contact must be provided in accordance with
all appropriate national and local regulations.
Steam
connection
(Steam direct)
Steam pressure
kPa
≤ 400
Boiling point
°C
≤ 152
Heater rating
kW
29
Volume flow
kg/h
46
Connection thread (on site)
Inch
½" internal thread
Steam valve, steam filter, steam stopcock and non-
return valve must be provided on site.
Note installation instructions for steam-heated Miele
washer-extractors.
Cold water
(Soft water)
Min. flow pressure
kPa
100
Max. pressure
kPa
1000
Volume flow necessary
l/min
26
Max. volume stream in absence of hot and raw water
supplies.
l/min
79.5
Special version, unit without detergent dispenser.
Volume flow necessary
l/min
20
Max. throughput (if hot and raw water supply is
not available)
l/min
77.5
On-site connection thread according to DIN 44 991
Inch
1" external thread
Length of supply hose
mm
1500
(supplied: 2 connection hoses + Y piece)
Water requirements with standard connection to hot
water in 60°C programme ( average value)
l/h
not yet available
In the absence of a hot water supply, connect to
alternative supply.
In the absence of a raw water supply, connect to
alternative supply.