R410A DC Inverter VRF V4 Plus Individual Series 50Hz
MCAC-VTSM-2014-04
74
Installation
For the capacity of outdoor unit is 32HP, the equivalent length of all pipes in this system is larger than 90m,
refer to table 3, the main pipe L1 is
Φ38.1/Φ22.2.
As the main pipe L1 is selected as
Φ31.8/
Φ
19.1 from step 2, and
Φ31.8/Φ19.1 from step 3, we finally select
the larger pipe
Φ38.1/Φ22.2 as main pipe L1.
Note: For the detail dimension and installation information pipe, please read the branch pipe installation manual carefully.