MCAC-VTSM-2014-04
R410A DC Inverter VRF V4 Plus Individual Series 50Hz
Installation
67
When the outdoor unit is lower than the surrounding obstacle, to avoid cross connection of the outdoor hot
air from affecting the heat exchange effect, please add an air director onto the exhaust hood of the
outdoor unit to facilitate heat dissipation. See the figure below. The height of the air director is HD (namely
H-h). Please make the air director on site.
If miscellaneous articles are piled around the outdoor unit, such articles must be 800mm below the top of
the outdoor unit. Otherwise, a mechanic exhaust device must be added.
4. Lifting method
Do not remove any package before the hoisting. Use two ropes to hoist the machine, keep the machine in
balance, and then raise it safely and steadily. In case of no package or if the package is damaged, use
plates or packing material to protect it.
When conveying and hoisting the outdoor unit, keep it upright, ensure that the slope does not exceed 30°,
and keep safety in mind.
Steel wire can be used for conveying:
Use 4 steel wires of the size above Φ6mm to convey the outdoor unit. Pay attention to the gravity center
and prevent sliding and tip-over of the outdoor unit.
In order to prevent scratch and deformity the outdoor unit, apply a guard board to the surface of contact
between the steel wire and the air conditioner.
Remove the cushion for use in the transport after finishing the transport.
Fork lifter can be used for conveying.
A
B
C
D
>45°
>1000mm
>300mm
Airflow deflector
Front view
B
A
B
A
C
D
Side view
B
A
Front view
Front view