R410A DC Inverter VRF V4 Plus Individual Series 50Hz
MCAC-VTSM-2014-04
22
Specifications & Performances
7. Electric characteristics
Model
Units
Power supply
Compressor
OFM
Hz
Voltage
(V)
Min.
(V)
Max
(V)
MCA
(A)
TOCA
(A)
MFA
(A)
MSC
(A)
RLA (A)
kW
FLA
(A)
MDV-730W/DRN1-i(C)
50
380~415
342
418
55.7
66
70
/
15.62+
9.8×3
0.52×2+0
.38×2
3.6×2+
2.7×2
MDV-785W/DRN1-i(C)
50
380~415
342
418
58.4
71.5
75
/
15.62+
9.8×3
0.52×2+0
.38×2
3.6×2+
2.7×2
MDV-850W/DRN1-i(C)
50
380~415
342
418
67.1
77.7
80
/
15.62+
9.8×4
0.52×2+0
.38×2
3.6×2+
2.7×2
MDV-900W/DRN1-i(C)
50
380~415
342
418
71.3
81.6
85
/
15.62+
9.8×4
0.52×2+0
.38×2
3.6×2+
2.7×2
Notes:
1. RLA is based on the following conditions, Indoor temp. 27°C DB/19°C WB, Outdoor temp. 35°C DB
2. TOCA means the total value of each OC set.
3. MSC means the Max. current during the starting of compressor.
4. Voltage range.
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above
listed range limits.
5. Maximum allowable voltage variation between phases is 2%
6. Selection wire size based on the larger value of MCA or TOCA
7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).
MCA:
Min. Circuit Amps. (A)
TOCA:
Total Over-current Amps. (A)
MFA:
Max. Fuse Amps. (A)
MSC:
Max. Starting Amps. (A)
RLA:
Rated Locked Amps. (A)
OFM:
Outdoor Fan Motor.
FLA:
Full Load Amps. (A)
KW:
Rated Motor Output (KW)