34
normal heating mode.
(1) The defrosting time is reached to the setting value.
(2) After defrosting for 3 minutes,T2
≥
2
℃
.
(3) If the defrosting time is between 2 and 4 minutes, T2
max-
T2
min
≥
2
℃
.
Defrosting action
:
Compressor
on
off
on
on
on
off
off
off
4-way valve
Outdoor fan
Indoor fan
Indoor fan breeze(10s)
DF-5
DF
Setting defrosting time
F8
DF-5
DF
DF=25SEC for 7k,9k,12k models and DF=45SEC for 21k,24k models.
8.4.3.5 High evaporator coil temp.T2 protection:
Model
TE7
TE8
TE9
7k
60
53
50
9k
60
53
50
12k
63
53
51
MS11D-12HRN1-QC2
(2T0032400212)
63
44
42
18k
60
53
50