31
When the evaporator coil temp.T2 keeps lower than TE5 for 5 minutes, the compressor and outdoor
fan will shut off.
When T2 is higher than TE6, the compressor and outdoor fan will restart up.
While TE5=4
℃
, TE 6=
10
℃
for 7k,9k,12k,18k models and TE5=3
℃
, TE 6=
14
℃
for 21,24 models.
8.4.3 Heating Mode (For Heating & Cooling model)
8.4.3.1 Compressor running rules:
When indoor room temp.T1 is higher than Tj, the compressor and outdoor fan will shut off. When T1 is
lower than Tk, the compressor and outdoor fan will start up.
TS+TB
T1
On
Off
TS+TB-2
While TB=2 for 7k,9k,12k,18k models and TB=0 for 21k,24k models
8.4.3.2 Outdoor fan running rules:
The outdoor units have single fan speed. The outdoor fan will run following the compressor except
when AC is in evaporator high temp. protection in heating mode , condenser high temp. protection in
cooling mode ,defrosting mode and the current protection.
8.4.3.3 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind
function has the priority.
Anti-cold wind function: