6.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
MS11D-07HRN1-QC2+
MOK3-07HN1-QC2
3/8’’
(Ф9.53)
1/4’’
(Ф6.35)
5
5
10
30
MS11D-07HRN1-QB6+
MOK-07HN1-QB6
MS11D-09HRN1-QB6+
MOK-09HN1-QB6
MS11D-09HRN1-QC2+
MOA2-09HN1-QC2
MS11D-12HRN1-QC2+
MOB4-12HN1-QC2
1/2’’
(Ф
12.7)
1/4’’
(Ф6.35)
5
5
10
30
MS11D-12HRN1-QB6+
MOA2-12HN1-QB6
MS11D-12HRN1-QC2+MOB-11HN1-QC2
MS11D-18HRN1-QB8+
MOC-18HN1-QB8
5
8
15
30
MS11D-18HRN1-QB6+
MOB-18HN1-QB6
MS11D-21HRN1-QB6W+
MOC-21HN1-QB6W
5/8’’
(Ф
16.0)
3/8’’
(Ф9.53)
5
10
20
60
MS11D-21HRN1-QB8+
MOP-21HN1-QB8W
MS11D-24HRN1-QB8W+
MOF2-24HN1-QB8W
MS11D-24HRN1-QB6W+
MOP-24HN1-QB6W
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
The oil trap should be installed per 5-7 meters.